{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-7HN46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-7HN46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-7HN46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7HN46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series molded case circuit breaker, 3VA2116-7HN46-0AA0, 4-pole, 160 A rated continuous current, ETU350 electronic trip unit, 800 V insulation voltage, line protection design.","salesMarkdown":"## What this MCCB is for The 800 V rated insulation voltage suits it for 400 V and 690 V line-to-line systems, though the interrupting capacity at 690 V drops to 3.7 kA, so it's best applied at 415 V or below where it delivers 242 kA breaking capacity. It's a step up from thermal-magnetic releases for selectivity coordination — you can dial in the long-time pickup and delay, short-time pickup and delay, and instantaneous pickup. That matters when you're cascading breakers downstream and need the upstream device to ride through a fault on a branch without tripping the main. No undervoltage release and no ground-fault monitoring are built in; those are add-on accessories if your application requires them. ## Panel fit and environment","metaTitle":"Siemens 3VA2116-7HN46-0AA0 SENTRON MCCB, 160A, 4-Pole, ETU35","metaDescription":"Siemens 3VA2116-7HN46-0AA0 SENTRON molded case circuit breaker, 160 A continuous, 4-pole, ETU350 electronic trip, 800 V insulation. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"1 600 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 50%; 100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=424804&mlfb=3VA2116-7HN46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7HN46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2116-7HN46-0AA0?","answer":"Submit an RFQ against this order code. We source it to order through independent distribution and confirm pricing and availability at quote time."},{"question":"What is the interrupting capacity of 3VA2116-7HN46-0AA0 at 415 V?","answer":"At 415 V the interrupting capacity is 242 kA. At 240 V it's 330 kA, and at 690 V it drops to 3.7 kA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-7HN46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-7HN46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}