{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-7JP46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-7JP46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-7JP46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7JP46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-7JP46-0AA0, molded case circuit breaker, 4-pole, 160 A, ETU550 electronic trip unit, line protection, 86 mm depth, 140 mm width, 181 mm height.","salesMarkdown":"The Siemens SENTRON 3VA2116-7JP46-0AA0 is a 4-pole molded case circuit breaker rated at a continuous current Iu of 160 A across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. The interrupting capacity reaches 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V. That spread means this breaker handles high-fault utility feeds at low voltage and still clears moderate faults at 690 V, which is useful for industrial distribution where the service voltage varies by region or transformer tap. The electronic trip unit is an ETU550, which supports communication functions — a step up from thermal-magnetic units for selectivity coordination and remote monitoring. The 3VA2116-7JP46-0AA0 measures 86 mm deep by 140 mm wide by 181 mm high. The 140 mm width for a 4-pole frame is standard for SENTRON 3VA breakers in this current class, so it will occupy the same DIN-rail or mounting-plate footprint as other 3VA 160 A 4-pole units. Maximum power loss is 25.5 W at rated current.","metaTitle":"Siemens 3VA2116-7JP46-0AA0 SENTRON MCCB, 160 A, 4-Pole, ETU5","metaDescription":"Siemens SENTRON 3VA2116-7JP46-0AA0 molded case circuit breaker, 160 A, 4-pole, ETU550 trip unit. Rated 330 kA at 240 V. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"4","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"160 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"240 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=188488&mlfb=3VA2116-7JP46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7JP46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2116-7JP46-0AA0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; the part is sourced through independent distribution channels and quoted to order."},{"question":"Will 3VA2116-7JP46-0AA0 drop into a panel that was specified around 3VA2110-8HN32-0AA0 without rewiring?","answer":"Both are 4-pole SENTRON 3VA breakers in the same frame size (140 mm wide for 160 A class), so the mounting footprint and bus-bar centers are identical. The difference is the trip unit: the 3VA2116-7JP46-0AA0 carries an ETU550 electronic trip unit with communication capability, whereas the 3VA2110-8HN32-0AA0 uses a different trip design. Wiring to the load terminals and bus connections will fit, but the control wiring for the communication function may need to be added if the original panel did not include it."},{"question":"What compliance documentation does this brand provide for 3VA2116-7JP46-0AA0 (RoHS, REACH, UL, IEC)?","answer":"Siemens SENTRON breakers are designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH declarations are available from Siemens documentation. The reference code per IEC 81346-2 is Q."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-7JP46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-7JP46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}