{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-7JQ32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-7JQ32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-7JQ32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7JQ32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-7JQ32-0AA0, 3-pole molded case circuit breaker, 160 A, ETU560 electronic trip unit, line protection.","salesMarkdown":"The Siemens 3VA2116-7JQ32-0AA0 is a 3-pole SENTRON molded case circuit breaker rated 160 A continuous from 40 °C all the way up to 70 °C — no derating needed across that span, which simplifies panel thermal budgeting for a line-up of these breakers. The N-conductor protection is adjustable from OFF up to 160 % of the phase rating, useful for sizing the neutral on a 4-wire system. Interrupting ratings: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V. That covers most industrial service-entrance and feeder applications where high fault current is expected. Rated insulation voltage Ui 800 V, operating temperature range -25 °C to 70 °C, storage from -40 °C to 80 °C. Maximum power loss 25.5 W — factor that into enclosure ventilation if you're packing several breakers side by side. Communication function is built in (ETU560 supports Modbus RTU via the optional COM module), so this breaker can report trip events, load currents, and alarm status to a PLC or BMS without extra signal wiring.","metaTitle":"Siemens 3VA2116-7JQ32-0AA0 SENTRON MCCB, 160 A, 3-pole, ETU5","metaDescription":"Siemens 3VA2116-7JQ32-0AA0 SENTRON molded case circuit breaker, 160 A continuous, 3-pole, ETU560 release, 330 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Courant permanent assigné Iu":"160 A","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg max.":"160 A","Adjustable response value current / lg min.":"32 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"240 A","Neutral conductors / upgradeable/retrofittable":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=390742&mlfb=3VA2116-7JQ32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7JQ32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2116-7JQ32-0AA0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through our independent distribution network."},{"question":"What is 3VA2116-7JQ32-0AA0's listed depth?","answer":"Depth is 86 mm (3.39 in). Width is 105 mm (4.13 in), height 181 mm (7.13 in)."},{"question":"Will 3VA2116-7JQ32-0AA0 drop into a panel specified around 3VA2110-8HN32-0AA0?","answer":"Both are 3-pole SENTRON 3VA-frame breakers with the same 105 mm width, 181 mm height, and 86 mm depth. The 3VA2116-7JQ32-0AA0 carries a higher 160 A continuous rating and the ETU560 electronic trip, while the 3VA2110-8HN32-0AA0 is a lower-current variant. Panel cutout and mounting are identical — no rewiring needed if the bus and cable sizing support 160 A."},{"question":"What compliance documentation does this brand provide?","answer":"Siemens SENTRON 3VA breakers are designed to IEC 60947-2 and carry CE, UKCA, and EAC markings. RoHS and REACH declarations are available from Siemens documentation portal. Specific UL listing varies by variant — verify UL file number for your jurisdiction."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-7JQ32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-7JQ32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}