{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-7JQ36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-7JQ36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-7JQ36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7JQ36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-7JQ36-0AA0, molded case circuit breaker, 3-pole, 160 A rated continuous current, line protection design, communication function, 330 kA interrupting capacity at 240 V.","salesMarkdown":"It carries a 330 kA interrupting capacity at 240 V, stepping down to 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V — high fault-current headroom for main or feeder protection where SCCR coordination matters. The breaker includes onboard communication capability, making it suitable for integration into monitored or smart distribution systems where remote trip indication or load data is required. Depth of 86 mm leaves clearance for rear bus connections and wiring ducts.","metaTitle":"Siemens 3VA2116-7JQ36-0AA0 SENTRON MCCB, 160 A, 3-pole, line","metaDescription":"Siemens SENTRON 3VA2116-7JQ36-0AA0 molded case circuit breaker, 160 A rated, 3-pole, 330 kA at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"240 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"32 A","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"160 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=312512&mlfb=3VA2116-7JQ36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7JQ36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2116-7JQ36-0AA0?","answer":"Submit an RFQ through this listing; we source and quote to order, with availability and current pricing confirmed at quote time."},{"question":"Will 3VA2116-7JQ36-0AA0 drop into a panel specified around 3VA2163-8JQ32-0AA0 without rewiring?","answer":"Both are SENTRON 3VA frame breakers with the same 105 mm width, 181 mm height, and 86 mm depth footprint, so they share the same panel cutout and bus-bar spacing. The 3VA2116-7JQ36-0AA0 is a 160 A line-protection breaker with communication; verify that the peer's trip unit and auxiliary wiring match your application before direct swap."},{"question":"What compliance documentation does this brand provide for 3VA2116-7JQ36-0AA0?","answer":"Siemens SENTRON MCCBs carry IEC/EN 60947-2 certification and are typically RoHS and REACH compliant. Specific declarations are available on request with an RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-7JQ36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-7JQ36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}