{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-7JQ46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-7JQ46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-7JQ46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7JQ46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-7JQ46-0AA0, molded case circuit breaker, 160 A continuous, 4-pole, 330 kA breaking capacity at 240 V, line protection, with communication function.","salesMarkdown":"Four poles handle three-phase plus neutral, and the interrupting capacity hits 330 kA at 240 V, 242 kA at 415 V, and still holds 187 kA at 500 V. That kind of short-circuit rating means it can sit on high-fault panels without cascading upstream breakers — a real advantage in industrial switchboards where available fault current is stiff. Width of 140 mm means it occupies three 45 mm module spaces on a DIN rail, typical for a 4-pole MCCB in this class.","metaTitle":"Siemens 3VA2116-7JQ46-0AA0 SENTRON MCCB, 160 A, 4-Pole, 330","metaDescription":"Siemens SENTRON 3VA2116-7JQ46-0AA0 molded case circuit breaker, 160 A continuous, 4-pole, 330 kA breaking capacity at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"240 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Initial Value":"32 A","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"160 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Summation current formation L + N conductor","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 100%","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=347027&mlfb=3VA2116-7JQ46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7JQ46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2116-7JQ46-0AA0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a quote request for current availability and pricing."},{"question":"What is 3VA2116-7JQ46-0AA0's listed depth?","answer":"The depth is 86 mm (3.39 in)."},{"question":"What is 3VA2116-7JQ46-0AA0's listed width?","answer":"The width is 140 mm (5.51 in)."},{"question":"Will 3VA2116-7JQ46-0AA0 drop into a panel specified around 3VA2116-5HM42-0CC0 without rewiring?","answer":"Both are 4-pole SENTRON MCCBs in the same physical frame size (181 x 140 x 86 mm), so the footprint is identical. However, the 3VA2116-5HM42-0CC0 may have different internal accessories or trip-unit settings — verify the terminal arrangement and auxiliary contact configuration against your panel wiring diagram before swapping."},{"question":"What compliance documentation does Siemens provide for 3VA2116-7JQ46-0AA0?","answer":"As a SENTRON MCCB, this part is designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH declarations are available from Siemens on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-7JQ46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-7JQ46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}