{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-7KP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-7KP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-7KP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7KP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2116-7KP36-0AA0, 160 A rated current, 3-pole, ETU850 electronic trip unit, line protection design.","salesMarkdown":"## Breaking capacity and what it means for your fault-current study This MCCB delivers 330 kA interrupting capacity at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V. ## Trip unit and protection curve The ETU850 is an electronic trip unit with adjustable protection parameters — it supports LSIG (long-time, short-time, instantaneous, ground-fault) functions, though this variant ships without ground-fault monitoring. The trip indicator is not fitted on this order code, so visual trip indication is not available at the breaker face. ## Thermal performance across ambient temperature Maximum power loss is 25.5 W at rated load. Dimensions are 181 mm high, 105 mm wide, 86 mm deep — a standard 3-pole MCCB footprint for the 3VA2 frame. The unit accepts screw-type lug connections; no special adapter plate needed for most switchboard cutouts.","metaTitle":"Siemens 3VA2116-7KP36-0AA0 SENTRON MCCB, 160 A, 3-Pole, ETU8","metaDescription":"Siemens 3VA2116-7KP36-0AA0 SENTRON molded case circuit breaker, 160 A continuous, 3-pole, ETU850 electronic trip unit, 330 kA at 240 V. Active production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"240 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=104476&mlfb=3VA2116-7KP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7KP36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2116-7KP36-0AA0?","answer":"Submit an RFQ against this order code. Pricing and availability are confirmed at quote time through independent distribution channels."},{"question":"What is the breaking capacity of this MCCB at 240 V?","answer":"330 kA at 240 V AC, which is the highest interrupting rating for this frame and suitable for high-fault-current service entrance applications."},{"question":"What trip unit does 3VA2116-7KP36-0AA0 use?","answer":"The ETU850 electronic trip unit, which supports adjustable LSIG protection curves (ground-fault monitoring not fitted on this variant)."},{"question":"What are the physical dimensions of this MCCB?","answer":"181 mm high, 105 mm wide, 86 mm deep — a standard 3-pole 3VA2 frame footprint."},{"question":"Does this breaker have communication capability?","answer":"Yes, the communication function is enabled on this order code, allowing integration with monitoring and control systems."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-7KP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-7KP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}