{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-7KQ36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-7KQ36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-7KQ36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7KQ36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, Molded case circuit breaker, 3VA2116-7KQ36-0AA0, 3-pole, 160 A continuous, line protection, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"## What this 3VA2116-7KQ36-0AA0 does in the panel The 3-pole construction and 800 V rated insulation voltage suit it for 400 V three-phase industrial feeds where you need a single breaker to handle the main or a heavy subfeed. What sets this MCCB apart is the interrupting capacity: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V. For a 160 A frame, that is serious fault-current headroom — you are not bumping into the breaker's limits on a stiff utility feed. Communication function is built in, so it can talk to a higher-level monitoring system for trip events and load data — useful when you want to know why a feeder dropped without walking the panel. The 160 A continuous rating is the breaker's thermal-magnetic or electronic trip threshold — it carries that current indefinitely at the listed ambient temperatures (–). The minimum setting of 240 A and maximum of 1 600 A refer to the adjustable trip unit range on this frame; you set the actual pickup within that window to match your load. For a 160 A feeder, you would dial the long-time pickup to 160 A or slightly above, depending on the load profile. The max power loss of 25.5 W matters for panel thermal design — if you are packing several breakers in a small enclosure, that heat adds up.","metaTitle":"Siemens 3VA2116-7KQ36-0AA0 SENTRON MCCB, 160 A, 3-Pole","metaDescription":"Siemens 3VA2116-7KQ36-0AA0 SENTRON molded case circuit breaker, 160 A continuous, 3-pole, line protection. Current lifecycle stage. Interrupting 330 kA at 240 V. Sourced to order a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"240 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"32 A","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"160 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU860","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=260433&mlfb=3VA2116-7KQ36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7KQ36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2116-7KQ36-0AA0's listed depth?","answer":"The depth is 86 mm (3.39 in), with a width of 105 mm (4.13 in) and height of 181 mm (7.13 in). These dimensions match the standard 3VA frame footprint."},{"question":"Will 3VA2116-7KQ36-0AA0 drop into a panel specified around 3VA2116-5HM42-0CC0 without rewiring?","answer":"Yes — both breakers share the same 3VA2116 frame dimensions (86 mm depth, 105 mm width, 181 mm height) and 3-pole configuration, so they fit the same panel cutout and bus connections. The difference is in the trip unit features: the -7KQ36-0AA0 adds communication and ground-fault monitoring that the -5HM42-0CC0 lacks."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-7KQ36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-7KQ36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}