{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-8HL32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-8HL32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-8HL32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-8HL32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 160, 3-pole circuit breaker, breaking capacity class L Icu=150kA @ 415V, line protection ETU320 LI, In=160A, with shunt trip left 208-277 V AC 50/60 Hz 220-250 V DC, 2 auxiliary switches.","salesMarkdown":"The 3VA2116-8HL32-0KC0 is a Siemens 3VA2 IEC frame 160 circuit breaker rated for a breaking capacity Icu of 150 kA at 415 V AC — that is the class L rating, meaning it can safely interrupt fault currents up to 150,000 A at that voltage without self-destructing. The ETU320 electronic trip unit provides LI (long-time and instantaneous) protection: overload protection Ir adjustable from 63 A to 160 A, and short-circuit protection Ii adjustable from 1.5 to 10 times In. That adjustability lets you coordinate with downstream devices without swapping trip units. ## Built-in accessories and panel integration This variant ships with a shunt trip wired left-side, operating on 208–277 V AC 50/60 Hz or 220–250 V DC, plus two auxiliary switches (changeover contacts). The shunt trip allows remote tripping from a safety circuit or E-stop string — common in machine-tool and conveyor applications where the breaker must open on a remote signal. The auxiliary switches report breaker status back to a PLC or indication lamp.","metaTitle":"Siemens 3VA2116-8HL32-0KC0 Circuit Breaker, 160A, 150kA @ 41","metaDescription":"Siemens 3VA2116-8HL32-0KC0 IEC frame 160 circuit breaker, 150kA breaking capacity at 415V, ETU320 LI protection, 160A. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1525645&mlfb=3VA2116-8HL32-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-8HL32-0KC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this circuit breaker?","answer":"The breaking capacity Icu is 150 kA at 415 V AC, which is the class L rating for the 3VA2 IEC frame 160."},{"question":"Where can I buy the 3VA2116-8HL32-0KC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-8HL32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-8HL32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}