{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-8HM32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-8HM32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-8HM32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-8HM32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-8HM32-0AA0, molded case circuit breaker, 3-pole, 160 A, ETU330 electronic trip unit, line protection version, breaking capacity 440 kA at 240 V.","salesMarkdown":"Insulation voltage is rated 800 V, and the interrupting ratings climb to 440 kA at 240 V, 330 kA at 415/440 V, 220 kA at 500 V, and 52.5 kA at 690 V — numbers that tell you this breaker is built for high-fault-capacity industrial mains, not branch panels. An optional motor drive extension is available for remote switching if the application needs it. Maximum power dissipation is 19.7 W — modest for a 160 A frame, but worth including in the panel thermal budget if several breakers sit side by side.","metaTitle":"Siemens 3VA2116-8HM32-0AA0 SENTRON MCCB, 160 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2116-8HM32-0AA0 molded case circuit breaker, 160 A continuous, 3-pole, ETU330 trip unit. Breaking capacity 440 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"440 kA","at 415 V":"330 kA","at 440 V":"330 kA","at 500 V":"220 kA","at 690 V":"52.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"160 A","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU330","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg max.":"160 A","Adjustable response value current / lg min.":"32 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"240 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"L","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=95748&mlfb=3VA2116-8HM32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-8HM32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2116-8HM32-0AA0 at 415 V?","answer":"330 kA at 415 V, which is the same rating as at 440 V. At 240 V it reaches 440 kA, and at 690 V it is still rated 52.5 kA."},{"question":"What trip unit does the 3VA2116-8HM32-0AA0 use?","answer":"The ETU330 electronic trip unit, which is the standard adjustable-release option on this SENTRON 3VA2 frame for line protection."},{"question":"Where can I buy 3VA2116-8HM32-0AA0 and how is it quoted?","answer":"It is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-8HM32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-8HM32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}