{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-8JQ32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-8JQ32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-8JQ32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-8JQ32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-8JQ32-0AA0, molded case circuit breaker, 3-pole, 160 A, ETU560 electronic trip unit, line protection, 440 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2116-8JQ32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel design in warm enclosures. The ETU560 electronic trip unit gives you adjustable time-current curves (tr from 0.5 to 20 s) and a short-time delay (tsd up to 0.5 s), so you can coordinate selectively downstream without sacrificing speed on hard faults. Communication function is built in — the ETU560 supports data exchange for power monitoring and remote trip indication, so you can wire it into a BMS or PLC without an add-on module.","metaTitle":"Siemens 3VA2116-8JQ32-0AA0 SENTRON MCCB, 160 A, 3-Pole, ETU5","metaDescription":"Siemens SENTRON 3VA2116-8JQ32-0AA0 molded case circuit breaker, 160 A, 3-pole, ETU560 release, 440 kA at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"440 kA","at 415 V":"330 kA","at 440 V":"330 kA","at 500 V":"220 kA","at 690 V":"53 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [in]":"3.4 in","Width [in]":"4.1 in","Height [in]":"7.1 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-40 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Summation current formation L-conductor","Design of the overcurrent release":"ETU560","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"20","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / lg max.":"160 A","Adjustable response value current / lg min.":"32 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"240 A","Adjustable response value current / lr min.":"64 A","Adjustable response value current / tg max.":"0.8 s","Adjustable response value current / tg min.":"0.05 s","Adjustable response value current / Isd max.":"1 600 A","Adjustable response value current / Isd min.":"96 A","Ground fault protection can be switched ON/OFF":"Yes","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSIG","Switching capacity class of the circuit breaker":"L","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=86746&mlfb=3VA2116-8JQ32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-8JQ32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2116-8JQ32-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — no stock or price figures are published here."},{"question":"What is 3VA2116-8JQ32-0AA0's listed depth?","answer":"The depth is 86 mm (3.4 in)."},{"question":"What is 3VA2116-8JQ32-0AA0's listed width?","answer":"The width is 105 mm (4.1 in)."},{"question":"What compliance documentation does this brand provide for 3VA2116-8JQ32-0AA0?","answer":"The SENTRON series typically carries UL, CSA, CE, and IEC certifications. Specific documentation (RoHS, REACH, UL, IEC) is available upon request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-8JQ32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-8JQ32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}