{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2125-6KQ46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2125-6KQ46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2125-6KQ46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2125-6KQ46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2125-6KQ46-0AA0, 4-pole molded case circuit breaker, line protection, 25 A continuous, 242 kA breaking at 240 V, 86 x 140 x 181 mm.","salesMarkdown":"Its breaking capacity hits 242 kA at 240 V and 187 kA at 415 V and 440 V — figures that put it in the high-interrupting class for industrial distribution panels where fault currents are serious. For a 25 A frame, that's enormous headroom — it's sized for the fault level at the service entrance or a large sub-distribution board, not for a downstream branch. The 3.7 kA rating at 690 V tells you the arc extinction gets harder at higher voltage, but that's still adequate for most 690 V industrial loads. The unit includes communication functionality and ground-fault monitoring via summation current formation on L + N conductors — meaning it can talk to a building management system or PLC and report trip events and leakage without a separate GFCI module. ## Panel fit and thermal derating No undervoltage release or voltage trip trigger on this variant, so it's a straight thermal-magnetic or electronic trip unit — no auxiliary coil to wire. That means no derating curve to calculate for warm enclosures — the breaker is already calibrated for a hot panel.","metaTitle":"Siemens 3VA2125-6KQ46-0AA0 SENTRON MCCB, 4-Pole, 25 A, 242 k","metaDescription":"Siemens 3VA2125-6KQ46-0AA0 SENTRON 4-pole molded case circuit breaker, 25 A continuous, 242 kA breaking at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"300 A","Minimum":"38 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"25 A","at 60 °C":"25 A","at 65 °C":"25 A","at 70 °C":"25 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Initial Value":"15 A","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"25 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"0.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Summation current formation L + N conductor","Continuous Current / Rated Value":"25 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU860","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 40% to 160%","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/641a6843e8dc2f758bb6426196efa871.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=424781&mlfb=3VA2125-6KQ46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2125-6KQ46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2125-6KQ46-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VA2125-6KQ46-0AA0's listed depth (86 mm) on this component line?","answer":"The depth is 86 mm (3.39 in), with a width of 140 mm (5.51 in) and height of 181 mm (7.13 in)."},{"question":"What compliance documentation does this brand provide for 3VA2125-6KQ46-0AA0?","answer":"As a Siemens SENTRON product, this MCCB is designed to meet IEC 60947-2 standards for molded case circuit breakers. Compliance documentation including RoHS and REACH declarations is typically available from Siemens' technical documentation portal for the 3VA series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2125-6KQ46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2125-6KQ46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}