{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5HL36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5HL36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5HL36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HL36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-5HL36-0AA0, 3-pole molded case circuit breaker, 63 A continuous, ETU320 electronic trip, 187 kA IC at 240 V.","salesMarkdown":"The 3VA2163-5HL36-0AA0: The ETU320 trip unit offers an adjustable overload range from 95 A minimum to 756 A maximum, giving flexibility for coordination with downstream protection. Sourced to order via RFQ. No known end-of-life notice as of this writing.","metaTitle":"Siemens 3VA2163-5HL36-0AA0 SENTRON MCCB, 63 A, 3-Pole, ETU32","metaDescription":"Siemens 3VA2163-5HL36-0AA0 SENTRON MCCB, 63 A continuous, 3-pole, ETU320 release. Active production, rated 187 kA at 240 V. Dimensions: 86x105x181 mm. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$421.27","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=294535&mlfb=3VA2163-5HL36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HL36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the physical dimensions?","answer":"86 mm deep, 105 mm wide, 181 mm high, IP40 front face."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5HL36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5HL36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}