{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5HL36-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5HL36-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5HL36-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HL36-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2163-5HL36-0CH0, 3-pole, 63 A, line protection, 187 kA at 240 V, with undervoltage release and auxiliary switches.","salesMarkdown":"## SENTRON 3VA2 MCCB — 63 A, 3-Pole Line Protection The 3VA2163-5HL36-0CH0: Rated 3-pole, it breaks up to 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. The 690 V figure is low, so verify system voltage against the curve before specifying for 690 V applications. No separate purchase needed for basic signaling — the kit is complete for a standard line-protection install. Dimensions are 181 mm height, 105 mm width, 86 mm depth — fits standard 3-pole MCCB panel cutouts and busbar centers.","metaTitle":"Siemens 3VA2163-5HL36-0CH0 SENTRON MCCB, 63 A, 3-Pole, 187 k","metaDescription":"Siemens 3VA2163-5HL36-0CH0 SENTRON molded case circuit breaker, 63 A continuous, 3-pole, 187 kA breaking at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"6.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21635HL360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=226552&mlfb=3VA2163-5HL36-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HL36-0CH0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this MCCB?","answer":"63 A continuous current (no derating from 40 °C to 70 °C), 3-pole, breaking capacity of 187 kA at 240 V, 121 kA at 415 V, 121 kA at 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. It includes an undervoltage release and 2 auxiliary switches plus a trip alarm switch."},{"question":"Where can I buy 3VA2163-5HL36-0CH0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What is the depth of this breaker?","answer":"The depth is 86 mm (3.39 in), with a width of 105 mm (4.13 in) and height of 181 mm (7.13 in). These are the body dimensions for panel cutout planning."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5HL36-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5HL36-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}