{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5HL36-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5HL36-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5HL36-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HL36-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, 3-pole molded case circuit breaker (MCCB), 63 A rated continuous current, 187 kA interrupting capacity at 240 V AC, line protection design with integrated shunt trip (STL).","salesMarkdown":"Interrupting capacity hits 187 kA at 240 V AC, stepping down to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. ## Current setting range and selectivity The electronic trip unit adjusts from 95 A minimum to 756 A maximum — that's a roughly 8:1 range, which gives the specifying engineer room to coordinate downstream feeders without swapping the breaker frame. The 63 A continuous rating is the thermal base; the adjustable trip covers the overload and short-circuit thresholds within that window. For a 480 V distribution panel, the 121 kA interrupting at 415 V/440 V means it can sit ahead of a 100 kA-rated downstream MCCB and still hold coordination. ## Shunt trip and auxiliary release The shunt trip is voltage-triggered (confirms a voltage trigger). No undervoltage release is fitted, so the breaker stays closed on control power loss unless the shunt trip is explicitly energized. That's the usual choice for applications where you don't want a nuisance trip on a 24 VDC dip. The 86 mm depth keeps it within typical 200 mm deep enclosure clearances.","metaTitle":"Siemens 3VA2163-5HL36-0HA0 SENTRON MCCB, 63 A, 187 kA IC","metaDescription":"Siemens 3VA2163-5HL36-0HA0 SENTRON 3-pole MCCB, 63 A rated, 187 kA interrupting at 240 V. Line protection with shunt trip. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21635HL360AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=149548&mlfb=3VA2163-5HL36-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HL36-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2163-5HL36-0HA0 at 240 V?","answer":"187 kA at 240 V AC. At 415 V and 440 V it's 121 kA, at 500 V it's 75.6 kA, and at 690 V it's 3.7 kA."},{"question":"Does 3VA2163-5HL36-0HA0 include a shunt trip?","answer":"Yes, it includes a shunt trip release (STL) for remote tripping. No undervoltage release is fitted."},{"question":"How do I get pricing and availability for 3VA2163-5HL36-0HA0?","answer":"Submit an RFQ through this listing. Current pricing and lead time are confirmed at quote time through independent distribution channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5HL36-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5HL36-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}