{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5HN32-0CA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5HN32-0CA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5HN32-0CA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HN32-0CA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-5HN32-0CA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 187 kA interrupting at 240 V, line protection design, includes undervoltage release.","salesMarkdown":"The Siemens SENTRON 3VA2163-5HN32-0CA0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current at 40 °C through 70 °C — no derating needed across that span, which simplifies panel layout when ambient runs warm. It carries 187 kA interrupting capacity at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V, so it handles high-fault service entrances and distribution feeders without cascading upstream. Dimensions are 181 mm high, 105 mm wide, 86 mm deep — standard SENTRON 3VA2 frame size, so it drops into existing 3VA cutouts without re-drilling. The UVR coil is factory-installed; no extra wiring for the release function.","metaTitle":"Siemens SENTRON 3VA2163-5HN32-0CA0 MCCB, 63 A, 3-Pole, 187 k","metaDescription":"Siemens SENTRON 3VA2163-5HN32-0CA0 molded case circuit breaker, 63 A rated, 3-pole, 187 kA interrupting at 240 V. Active production. Undervoltage release included. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"756 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"6.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21635HN320AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=319035&mlfb=3VA2163-5HN32-0CA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HN32-0CA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2163-5HN32-0CA0 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VA2163-5HN32-0CA0's interrupting capacity at 240 V?","answer":"187 kA at 240 V. Also rated 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V."},{"question":"Does 3VA2163-5HN32-0CA0 include an undervoltage release?","answer":"Yes, it ships with an undervoltage release (UVR) fitted. The release design is an undervoltage release (UVR) type."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5HN32-0CA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5HN32-0CA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}