{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5HN36-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5HN36-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5HN36-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HN36-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-5HN36-0HC0, molded case circuit breaker, 3-pole, 63 A, breaking capacity 187 kA at 240 V, 121 kA at 415 V, with shunt trip and 2 auxiliary switches.","salesMarkdown":"## Line protection MCCB with shunt trip and auxiliary switches Its 3-pole design carries a breaking capacity of 187 kA at 240 V AC, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V, giving you selectivity headroom for high-fault installations like transformer secondaries or large motor control centers. The unit includes an integrated shunt trip (STL) and two auxiliary switches (HQ), so it arrives ready for remote tripping and status feedback without adding accessory modules. The depth of 86 mm (3.39 in) leaves clearance for rear-access wiring in enclosures with shallow gland plates. Maximum power loss is 4 W, so heat buildup in a sealed cabinet is minimal.","metaTitle":"Siemens 3VA2163-5HN36-0HC0 SENTRON MCCB, 63 A, 187 kA at 240","metaDescription":"Siemens SENTRON 3VA2163-5HN36-0HC0 molded case circuit breaker, 63 A, 3-pole, 187 kA breaking capacity at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"756 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21635HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=424682&mlfb=3VA2163-5HN36-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HN36-0HC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2163-5HN36-0HC0?","answer":"Submit an RFQ through this listing; availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What are the key ratings of this MCCB?","answer":"Continuous current is 63 A (no derating up to 70 °C), breaking capacity is 187 kA at 240 V, 121 kA at 415/440 V, and 75.6 kA at 500 V. It is a 3-pole line-protection device with a shunt trip and two auxiliary switches."},{"question":"What are the physical dimensions of 3VA2163-5HN36-0HC0?","answer":"Width 105 mm (4.13 in), height 181 mm (7.13 in), depth 86 mm (3.39 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5HN36-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5HN36-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}