{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5HN36-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5HN36-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5HN36-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HN36-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2163-5HN36-0KL0, 63 A rated continuous current, 3-pole, ETU350 electronic trip unit, line protection version.","salesMarkdown":"The shunt trip release (STL) is built in, so remote tripping via a pushbutton or safety relay is ready out of the box. Above that, it derates linearly: 60.6 A at 55 °C, 58.3 A at 60 °C, 55.9 A at 65 °C, and 53.6 A at 70 °C (–). For a panel OEM stuffing this into a 105 mm wide × 181 mm high × 86 mm deep (–) enclosure, the derating curve means you can push the full 63 A up to 50 °C ambient — common in ventilated industrial panels — but need to account for the drop in sealed, high-temp cabinets. The 4 W maximum power loss is modest; heat dissipation won't drive fan sizing on its own. The line and load terminals accept copper or aluminum conductors up to the manufacturer's specified lug range; the integrated shunt trip (STL) wiring lands on the auxiliary terminal block, keeping control wiring separate from the power path. The trip indicator gives a visual red flag when the breaker has tripped on fault, not just been switched off — useful for field service techs troubleshooting a downstream short.","metaTitle":"Siemens 3VA2163-5HN36-0KL0 SENTRON MCCB, 63 A, 3-Pole, ETU35","metaDescription":"Siemens SENTRON 3VA2163-5HN36-0KL0 molded case circuit breaker, 63 A rated, 3-pole, ETU350 electronic trip unit. Breaking capacity 187 kA at 240 V. Current lifecycle stage. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"4 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-5HN36-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"756 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"630 A","Adjustable response value current / Isd min.":"95 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=493809&mlfb=3VA2163-5HN36-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5HN36-0KL0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2163-5HN36-0KL0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time; no stock count or price figure is published here."},{"question":"What are the key ratings of 3VA2163-5HN36-0KL0?","answer":"Rated continuous current Iu is 63 A, with breaking capacity of 187 kA at 240 V and 121 kA at 415 V. It is a 3-pole MCCB with an ETU350 electronic trip unit and a built-in shunt trip release."},{"question":"What compliance documentation is available for this MCCB?","answer":"As a Siemens SENTRON product, the 3VA2163-5HN36-0KL0 carries IEC 60947-2 certification for molded case circuit breakers. RoHS and REACH declarations are available from the manufacturer. Specific UL listing should be verified against the nameplate marking on the unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5HN36-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5HN36-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}