{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5JP32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5JP32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5JP32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5JP32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-5JP32-0HA0, molded case circuit breaker, 3-pole, 63 A, ETU550 electronic trip unit, line protection, 187 kA at 240 V.","salesMarkdown":"## 63 A MCCB with ETU550 — breaking capacity and thermal curve The interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V — so the high short-circuit ratings at typical distribution voltages mean this breaker can sit close to the transformer without needing upstream current-limiting fuses. Thermal derating is minimal up to 50 °C (full 63 A), then drops to 60.6 A at 55 °C, 58.3 A at 60 °C, 55.9 A at 65 °C, and 53.6 A at 70 °C. That curve matters when the breaker lives in a crowded panel or near heat sources — the 70 °C rating is still 85% of the nominal, so you don't lose much headroom in a warm enclosure. The breaker measures 105 mm wide, 181 mm tall, and 86 mm deep — standard 3-pole MCCB footprint for the SENTRON 3VA2 frame. The ETU550 electronic trip unit supports communication and includes a voltage trigger. The basic switch element carries order code 3VA2163-5JP32-0AA0. Maximum power loss is 4 W. Mechanical endurance is 20,000 operations.","metaTitle":"Siemens 3VA2163-5JP32-0HA0 SENTRON MCCB, 63A, 3-Pole, ETU550","metaDescription":"Siemens 3VA2163-5JP32-0HA0 SENTRON molded case circuit breaker, 63A rated continuous current, 3-pole, ETU550 electronic trip unit, 187kA at 240V. Active production. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"4 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-5JP32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU550","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"95 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"630 A","Adjustable response value current / Isd min.":"38 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=530238&mlfb=3VA2163-5JP32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5JP32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"At 240 V the interrupting capacity is 187 kA; at 415 V and 440 V it is 121 kA; at 500 V it is 79 kA; at 690 V it is 4.25 kA."},{"question":"What trip unit does this 3VA2163-5JP32-0HA0 use?","answer":"It uses the ETU550 electronic trip unit, configured for line protection, with communication capability and a voltage trigger."},{"question":"Where can I buy 3VA2163-5JP32-0HA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5JP32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5JP32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}