{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5MN32-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5MN32-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5MN32-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5MN32-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series molded case circuit breaker, 3VA2163-5MN32-0KA0, 3-pole, 63 A, 187 kA interrupting at 240 V, motor protection design with shunt trip release.","salesMarkdown":"## 63 A MCCB with serious interrupting muscle The Siemens 3VA2163-5MN32-0KA0 is a 3-pole SENTRON molded case circuit breaker rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed in a warm panel. Interrupting capacity hits 187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3.7 kA at 690 V. That's selectivity headroom for a main breaker feeding downstream distribution in an industrial switchboard. The 4 W maximum power loss is modest; no forced ventilation needed in a typical enclosure.","metaTitle":"Siemens 3VA2163-5MN32-0KA0 SENTRON MCCB, 63 A, 187 kA at 240","metaDescription":"Siemens 3VA2163-5MN32-0KA0 SENTRON molded case circuit breaker, 63 A continuous, 187 kA interrupting at 240 V. Motor protection design with shunt trip. Active production, sourced t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21635MN320AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"18 500 W","operating power / at AC-3 / at 400 V":"30 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"E","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569559&mlfb=3VA2163-5MN32-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5MN32-0KA0/alternatives.json"},"ai":{"faq":[{"question":"What does the shunt trip release do on this breaker?","answer":"The shunt trip (STL) auxiliary release allows remote tripping from a safety circuit or PLC output — standard for emergency-stop chains on motor-protection panels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5MN32-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5MN32-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}