{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5MN36-0CA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5MN36-0CA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5MN36-0CA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5MN36-0CA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-5MN36-0CA0, molded case circuit breaker, 3-pole, 63 A, motor protection with ETU350M electronic release, 187 kA at 240 V, undervoltage release, phase failure detection.","salesMarkdown":"## 63 A MCCB with ETU350M — motor protection that tracks the pressure curve The ETU350M electronic release gives you adjustable overload and short-circuit curves, so you can dial in the trip characteristic to match the inrush and running profile of a pump, conveyor, or compressor — every shot the same, no nuisance trips on start-up. ## Interrupting capacity — selectivity headroom across voltage tiers This MCCB delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. At 105 mm wide by 86 mm deep by 181 mm tall, this breaker fits a standard MCCB footprint. The 3-pole block with undervoltage release (UVR) and phase failure detection built in means no external relay for loss-of-phase protection — one less device to wire and one less terminal to torque. Maximum power loss is 75 W, so account for that heat in a sealed enclosure. At 55 °C it derates to 60.48 A, at 60 °C to 59.22 A, at 65 °C to 57.96 A, and at 70 °C to 56.7 A.","metaTitle":"Siemens 3VA2163-5MN36-0CA0 SENTRON MCCB, 63 A, 187 kA at 240","metaDescription":"Siemens 3VA2163-5MN36-0CA0 SENTRON molded case circuit breaker, 63 A rated, 187 kA interrupting at 240 V. Motor protection with ETU350M release, undervoltage release, phase failure","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"No","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-5MN36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"22 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"945 A","Adjustable response value current / li min.":"945 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"945 A","Adjustable response value current / Isd min.":"189 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569576&mlfb=3VA2163-5MN36-0CA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5MN36-0CA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2163-5MN36-0CA0 at 415 V?","answer":"121 kA at 415 V, matching the 440 V rating. At 240 V it reaches 187 kA."},{"question":"Does this MCCB include phase failure protection?","answer":"Yes, phase failure detection is built in — no external phase-loss relay needed."},{"question":"Where can I buy 3VA2163-5MN36-0CA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What overcurrent release does this breaker use?","answer":"The ETU350M electronic release — adjustable overload and short-circuit curves for motor protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5MN36-0CA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5MN36-0CA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}