{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5MN36-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5MN36-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5MN36-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5MN36-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-5MN36-0DC0, molded case circuit breaker, 3-pole, 63 A, motor protection design, undervoltage release, 2 auxiliary switches HQ, 187 kA at 240 V.","salesMarkdown":"## 63 A MCCB with motor protection and undervoltage release The interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V, so it handles high-fault industrial service entrances and motor branch circuits with substantial SCCR headroom. ## Built-in protection and auxiliary functions Two auxiliary switches HQ are supplied with the basic switch. No ground-fault monitoring version is included, and no communication function is onboard. The 86 mm depth is within typical enclosure clearance for 3-pole MCCBs in motor control centers. Maximum power loss is 6.5 W, which matters for thermal budgeting inside sealed enclosures.","metaTitle":"Siemens 3VA2163-5MN36-0DC0 SENTRON MCCB, 63 A, 3-Pole, Motor","metaDescription":"Siemens SENTRON 3VA2163-5MN36-0DC0 molded case circuit breaker, 63 A rated, 3-pole, motor protection design with undervoltage release and phase failure detection. Breaking capacity","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"6.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21635MN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"18 500 W","operating power / at AC-3 / at 400 V":"30 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"E","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569657&mlfb=3VA2163-5MN36-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5MN36-0DC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2163-5MN36-0DC0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2163-5MN36-0DC0 at different voltages?","answer":"The interrupting capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V."},{"question":"Does 3VA2163-5MN36-0DC0 include undervoltage release and phase failure detection?","answer":"Yes, it includes an undervoltage release (UVR) as the auxiliary release and phase failure detection as standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5MN36-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5MN36-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}