{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-5MN36-0DH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-5MN36-0DH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-5MN36-0DH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5MN36-0DH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-5MN36-0DH0, molded case circuit breaker, 3-pole, 63 A, 187 kA at 240 V, motor protection version with ETU350M electronic trip unit.","salesMarkdown":"## MCCB for motor protection — 63 A, 187 kA SCCR The Siemens SENTRON 3VA2163-5MN36-0DH0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current (Iu) at up to 50 °C ambient, with an interrupting capacity of 187 kA at 240 V AC. This is the motor protection version, fitted with an ETU350M electronic overcurrent release and an undervoltage release (UVR). At 415 V and 440 V the rating holds at 121 kA; at 690 V it still manages 17 kA. The breaker holds full 63 A rating through 50 °C ambient. Above that, derate linearly: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. Maximum power loss is 75 W — account for that in enclosure thermal calculations. ## Integrated auxiliary and alarm contacts Phase failure detection is standard.","metaTitle":"Siemens 3VA2163-5MN36-0DH0 SENTRON MCCB, 63 A, 187 kA at 240","metaDescription":"Siemens SENTRON 3VA2163-5MN36-0DH0 molded case circuit breaker, 63 A rated, 187 kA at 240 V interrupting capacity. Motor protection version with ETU350M release. Current lifecycle.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-5MN36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"22 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"945 A","Adjustable response value current / li min.":"945 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"945 A","Adjustable response value current / Isd min.":"189 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569658&mlfb=3VA2163-5MN36-0DH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-5MN36-0DH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2163-5MN36-0DH0?","answer":"This MCCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting capacity of 3VA2163-5MN36-0DH0 at 240 V?","answer":"The interrupting capacity is 187 kA at 240 V AC. At 415 V and 440 V it is 121 kA; at 500 V it is 75.6 kA; at 690 V it is 17 kA."},{"question":"What type of trip unit does 3VA2163-5MN36-0DH0 use?","answer":"It uses an ETU350M electronic overcurrent release, designed for motor protection applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-5MN36-0DH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-5MN36-0DH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}