{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-6HL32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-6HL32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-6HL32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6HL32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2163-6HL32-0AB0, 63 A, 3-pole, ETU320 electronic trip unit, line protection, 242 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2163-6HL32-0AB0 is a 3-pole molded case circuit breaker rated at 63 A continuously from 40 °C all the way up to 70 °C — no derating curve to chase across the panel ambient range. That flat thermal rating simplifies BOM planning for enclosures that run warm. Breaking capacity reaches 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V — high enough for most transformer-fed industrial service entrances and large motor control centers. Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint that drops into existing SENTRON 3VA2 panel cutouts and busbar systems. The breaker ships with two HP auxiliary switches integrated, so you get status feedback without adding external contact blocks. Maximum power loss is 4 W, which keeps heat rise low in a dense panel.","metaTitle":"Siemens 3VA2163-6HL32-0AB0 SENTRON MCCB, 63 A, 3-Pole, ETU32","metaDescription":"Siemens SENTRON 3VA2163-6HL32-0AB0 MCCB, 63 A at 70 °C, 3-pole, ETU320 trip unit. Breaking capacity 242 kA at 240 V. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA21636HL320AA0","Courant permanent assigné Iu":"63 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"95 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=13892&mlfb=3VA2163-6HL32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6HL32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA2163-6HL32-0AB0 and how is it quoted for volume purchases?","answer":"This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is 3VA2163-6HL32-0AB0's listed depth?","answer":"The depth is 86 mm (3.39 in), which fits standard 200 mm deep enclosures with rear busbar clearance."},{"question":"What is 3VA2163-6HL32-0AB0's listed width?","answer":"The width is 105 mm (4.13 in), matching the standard 3-pole MCCB footprint for SENTRON 3VA2 panels."},{"question":"Will 3VA2163-6HL32-0AB0 drop into a panel specified around 3VA2163-8HM32-0AA0 without rewiring?","answer":"Both are 3-pole SENTRON 3VA2 breakers with identical 105 mm width, 181 mm height, and 86 mm depth — same footprint and busbar pitch, so no rewiring needed for the panel cutout. Verify the trip unit and auxiliary contact configuration match your protection scheme."},{"question":"What compliance documentation does Siemens provide for 3VA2163-6HL32-0AB0?","answer":"As a SENTRON 3VA2 series MCCB, it carries CE marking for the European market and is designed to meet IEC 60947-2. RoHS and REACH declarations are available from Siemens on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-6HL32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-6HL32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}