{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-6HL32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-6HL32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-6HL32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6HL32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-6HL32-0DA0, molded case circuit breaker, 3-pole, 63 A rated continuous current Iu, ETU320 electronic trip unit, 242 kA breaking capacity at 240 V, undervoltage release, line protection version.","salesMarkdown":"The Siemens 3VA2163-6HL32-0DA0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current at 40 °C, with a 242 kA interrupting capacity at 240 V — that figure drops to 187 kA at 415 V and 121 kA at 500 V, so the SCCR you design to depends on your system voltage. The 63 A rating holds flat from 40 °C through 50 °C, then derates to 60.6 A at 55 °C and 53.5 A at 70 °C — so in a warm enclosure you lose about 15 % of capacity at the top end. Dimensions are 105 mm wide × 181 mm high × 86 mm deep — the 105 mm width is a standard 3-pole MCCB footprint for the SENTRON 3VA2 frame, so it drops into existing panel cutouts and busbar systems designed for that frame.","metaTitle":"Siemens 3VA2163-6HL32-0DA0 SENTRON MCCB, 63 A, 242 kA","metaDescription":"Siemens SENTRON 3VA2163-6HL32-0DA0 molded case circuit breaker, 3-pole, 63 A rated, 242 kA at 240 V. ETU320 trip unit, undervoltage release. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"6.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-6HL32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"95 A","Adjustable response value current / lr min.":"25 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=283467&mlfb=3VA2163-6HL32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6HL32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2163-6HL32-0DA0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of 3VA2163-6HL32-0DA0 at different voltages?","answer":"242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V. The rating drops significantly above 500 V, so verify system voltage against the curve before specifying."},{"question":"What trip unit does the 3VA2163-6HL32-0DA0 use?","answer":"It uses an ETU320 electronic trip unit, configured for line protection. The undervoltage release (UVR) is integrated as standard."},{"question":"Will 3VA2163-6HL32-0DA0 fit a panel designed for a 3VA1010-2ED32-0JA0?","answer":"The 3VA2163 is a larger frame (105 mm wide vs the 3VA1010's narrower 2-pole or smaller frame width) and higher current rating. It will not drop into the same cutout without panel modification — check the busbar and mounting hole pattern before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-6HL32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-6HL32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}