{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-6HN32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-6HN32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-6HN32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6HN32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA2163-6HN32-0AA0, 63 A, 3-pole, ETU350 electronic trip unit, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2163-6HN32-0AA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current, with no derating needed from 40 °C up through 70 °C — the full 63 A holds across that entire ambient span. That flat thermal curve simplifies panel sizing in warm enclosures or near other heat sources. The interrupting capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, and 121 kA at 500 V; at 690 V it drops to 3.7 kA, so verify your available fault current at the system voltage. No undervoltage release, no voltage trigger, no communication function, and no ground-fault monitoring — this is a straight line-protection breaker with the ETU350 trip unit as the only adjustable element. Power loss is rated at a maximum of 4 W.","metaTitle":"Siemens 3VA2163-6HN32-0AA0 SENTRON MCCB, 63 A, 3-Pole, ETU35","metaDescription":"Siemens SENTRON 3VA2163-6HN32-0AA0 molded case circuit breaker. 63 A continuous, 3-pole, ETU350 electronic trip. Interrupting 242 kA at 240 V. Current lifecycle stage. Sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"756 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$254.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=390690&mlfb=3VA2163-6HN32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6HN32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2163-6HN32-0AA0 at 415 V?","answer":"187 kA at 415 V, and the same rating at 440 V. At 240 V it reaches 242 kA; at 500 V it is 121 kA; at 690 V it drops to 3.7 kA."},{"question":"Will 3VA2163-6HN32-0AA0 drop into a panel specified for 3VA1110-5ED32-0AA0?","answer":"Not without checking the footprint and trip unit compatibility. The 3VA2163 is a 3-pole 63 A breaker with an ETU350 electronic trip; the 3VA1110 series uses a different frame size and trip technology. Panel cutouts, busbar spacing, and wiring may differ — verify the mounting dimensions and terminal layout before substitution."},{"question":"How do I get current pricing and availability for 3VA2163-6HN32-0AA0?","answer":"Submit an RFQ through this listing. The part is sourced to order via independent distribution channels; current pricing and lead time are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-6HN32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-6HN32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}