{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-6HN32-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-6HN32-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-6HN32-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6HN32-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-6HN32-0AE0, molded case circuit breaker, 3-pole, line protection, 63 A (40-50 °C), 242 kA at 240 V, ETU350 electronic trip unit, 4 auxiliary switches HQ, IP40 front.","salesMarkdown":"The Siemens 3VA2163-6HN32-0AE0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated 63 A continuously from 40 °C through 50 °C ambient — no derating needed in a standard 40 °C panel. Above that, the ETU350 electronic trip unit follows a controlled derating curve: 60.6375 A at 55 °C, 58.275 A at 60 °C, 55.9125 A at 65 °C, and 53.55 A at 70 °C. For a panel builder sizing a 63 A feeder in a 50 °C enclosure, this breaker delivers full rating without oversizing the frame. ## Breaking capacity by voltage The interrupting rating scales with system voltage: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V. ## Trip unit and auxiliary configuration The basic switch assembly code is 3VA2163-6HN32-0AA0.","metaTitle":"Siemens 3VA2163-6HN32-0AE0 SENTRON MCCB, 63 A, 242 kA","metaDescription":"Siemens SENTRON 3VA2163-6HN32-0AE0 molded case circuit breaker, 3-pole, 63 A rated at 40-50 °C, 242 kA breaking at 240 V. ETU350 trip unit. Current lifecycle stage. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","Auxiliary contact version":"4 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2163-6HN32-0AA0","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Undervoltage Release With Leading Contact":"No","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg min.":"0.4 s","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"756 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"Lug terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=197269&mlfb=3VA2163-6HN32-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6HN32-0AE0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2163-6HN32-0AE0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time against your target quantity and delivery window — no automated price or lead-time figure is published here."},{"question":"What is 3VA2163-6HN32-0AE0's depth and width for panel cutout planning?","answer":"Depth is 86 mm, width is 105 mm, height is 181 mm. These match the standard SENTRON 3VA2 panel cutout footprint."},{"question":"Will 3VA2163-6HN32-0AE0 drop into a panel specified around 3VA2163-5HL32-0JB0 without rewiring?","answer":"Both are 3-pole SENTRON 3VA2 frame breakers with the same 105 mm width and 181 mm height, so the mechanical fit and busbar connection points are identical. The difference is in the trip unit and auxiliary configuration — the -6HN32 variant carries an ETU350 electronic trip with 4 HQ auxiliaries, while the -5HL32 uses a different trip and auxiliary count. No rewiring needed for the power circuit, but verify the auxiliary wiring map matches your control scheme."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-6HN32-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-6HN32-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}