{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-6KP42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-6KP42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-6KP42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6KP42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-6KP42-0AA0, 4-pole molded case circuit breaker, 63 A, ETU850 electronic release, line protection version, 242 kA interrupting at 240 V.","salesMarkdown":"## SENTRON 3VA2163-6KP42-0AA0 — 63 A MCCB with ETU850 Release The Siemens SENTRON 3VA2163-6KP42-0AA0 is a 4-pole molded case circuit breaker rated for a continuous current of 63 A across the full ambient range from 40 °C to 70 °C, with no derating required. The interrupting ratings are class-leading: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.8 kA at 690 V. The breaker occupies 140 mm width, 181 mm height, and 86 mm depth — a compact footprint for a 4-pole MCCB with integral electronic trip. Panel cutout and busbar spacing should be verified against the existing layout, but the dimensions align with the SENTRON 3VA2 frame family, so a panel designed for a 3VA2 breaker will accept this unit without rewiring. Front-face protection is IP40, sufficient for enclosed distribution boards. The ETU850 release includes a communication function, enabling integration with energy management or remote monitoring systems via the SENTRON communication bus.","metaTitle":"Siemens 3VA2163-6KP42-0AA0 SENTRON MCCB, 63 A, 242 kA at 240","metaDescription":"Siemens SENTRON 3VA2163-6KP42-0AA0 molded case circuit breaker, 4-pole, 63 A, ETU850 release, 242 kA at 240 V. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.8 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [in]":"3.4 in","Width [in]":"5.5 in","Height [in]":"7.1 in","Number of poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-40 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Design of the N-conductor protection":"adjustable OFF; 40% bis160%","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"95 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"630 A","Adjustable response value current / Isd min.":"38 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=2947&mlfb=3VA2163-6KP42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-6KP42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit does 3VA2163-6KP42-0AA0 use?","answer":"It uses the ETU850 electronic trip unit, which provides adjustable long-time (tr), short-time, instantaneous, and ground-fault protection. The long-time delay is adjustable from 0.5 s to 25 s."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-6KP42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-6KP42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}