{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7HN32-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7HN32-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7HN32-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7HN32-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-7HN32-0AG0, molded case circuit breaker, 3-pole, 63 A continuous rating at 40 °C, 330 kA breaking capacity at 240 V AC, line protection design.","salesMarkdown":"## 63 A MCCB with 330 kA interrupting capacity The Siemens 3VA2163-7HN32-0AG0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to 70 °C, which simplifies panel design in warm enclosures. At 415 V and 440 V the interrupting rating holds at 242 kA; at 690 V it drops to 3.7 kA, so verify the available fault current at your service voltage. ## Line protection design with auxiliary switching That dual-signal feedback is useful for remote fault annunciation without extra wiring. The basic switch variant is 3VA2163-7HN32-0AA0; this order code adds the auxiliary switch package. Dimensions are 181 mm height, 105 mm width, and 86 mm depth. The 105 mm width is standard for a 3-pole SENTRON 3VA2 frame — it occupies three 35 mm DIN-rail modules (each pole roughly 35 mm). ## Power loss and environmental limits Maximum power loss is 4 W at rated current — negligible for thermal budget calculations in a crowded panel. The MCCB includes a trip indicator (mechanical flag) for visual confirmation of a tripped state.","metaTitle":"Siemens 3VA2163-7HN32-0AG0 SENTRON MCCB, 63 A, 3-Pole, 330 k","metaDescription":"Siemens 3VA2163-7HN32-0AG0 SENTRON molded case circuit breaker, 63 A continuous, 3-pole, 330 kA at 240 V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"756 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2163-7HN32-0AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HP","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=78948&mlfb=3VA2163-7HN32-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7HN32-0AG0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2163-7HN32-0AG0 at different voltages?","answer":"At 240 V AC the interrupting rating is 330 kA; at 415 V and 440 V it is 242 kA; at 500 V it is 187 kA; at 690 V it drops to 3.7 kA. Verify the available fault current at your service voltage before specifying."},{"question":"Where can I buy 3VA2163-7HN32-0AG0 and how is it quoted?","answer":"This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"Does this MCCB include auxiliary contacts?","answer":"Yes, it is fitted with one auxiliary switch and one trip alarm switch (HP type), providing both a position-follow contact and a separate trip-indicating contact."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7HN32-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7HN32-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}