{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7HN32-0DH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7HN32-0DH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7HN32-0DH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7HN32-0DH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2163-7HN32-0DH0, 63 A, 3-pole, line protection, ETU350 electronic trip unit, 330 kA breaking capacity at 240 V AC.","salesMarkdown":"Its interrupting capacity reaches 330 kA at 240 V AC, stepping down to 242 kA at 415 V and 440 V, then 187 kA at 500 V, and 5.25 kA at 690 V — the voltage-dependent curve is typical for current-limiting MCCBs and governs where this breaker can be placed in the fault-current hierarchy. The 63 A rating holds flat from 40 °C through 50 °C ambient, then derates linearly to 53.55 A at 70 °C. That means in a warm panel (55 °C+) you lose roughly 4–15 % of headroom — plan the load accordingly if the breaker sits near other heat sources. The ETU350 trip unit is electronic, not thermal-magnetic, so it offers better precision and adjustable long-time, short-time, and instantaneous pickup thresholds. That covers remote status indication and undervoltage shutdown without needing an external relay. Dimensions are 105 mm wide, 181 mm high, 86 mm deep — a standard 3-pole MCCB footprint that fits SENTRON 3VA2 mounting accessories and busbar systems. The 86 mm depth includes the arc-chamber housing; verify gland-plate clearance if the panel is shallow.","metaTitle":"Siemens 3VA2163-7HN32-0DH0 SENTRON MCCB, 63 A, 3-Pole, 330 k","metaDescription":"Siemens SENTRON 3VA2163-7HN32-0DH0 molded case circuit breaker, 63 A, 3-pole, line protection, ETU350 trip unit, 330 kA at 240 V. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"5.25 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"6.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-7HN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"756 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"630 A","Adjustable response value current / Isd min.":"95 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=254611&mlfb=3VA2163-7HN32-0DH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7HN32-0DH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"242 kA at 415 V AC, same as at 440 V. The rating drops to 187 kA at 500 V and 5.25 kA at 690 V."},{"question":"What trip unit does 3VA2163-7HN32-0DH0 use?","answer":"An ETU350 electronic overcurrent release, adjustable for long-time, short-time, and instantaneous protection. No ground-fault or phase-failure detection on this variant."},{"question":"Where can I buy 3VA2163-7HN32-0DH0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — no fixed stock count or lead time is published here."},{"question":"Does 3VA2163-7HN32-0DH0 include an undervoltage release?","answer":"Yes, an undervoltage release (UVR) is integrated, designated 3VA9608-0BB25. The auxiliary contact block provides 2 auxiliary switches plus 1 trip alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7HN32-0DH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7HN32-0DH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}