{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7HN32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7HN32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7HN32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7HN32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA2163-7HN32-0JL0, 3-pole, 63 A, ETU350 electronic trip unit, 330 kA at 240 V, line protection version.","salesMarkdown":"The 63 A rating holds flat from 40 °C through 50 °C, then derates to 60.6 A at 55 °C and 53.6 A at 70 °C. That 105 mm width is three pole spaces on a standard 35 mm DIN rail — it occupies the same footprint as a 3-pole frame from the 3VA1 or 3VA2 family, so a panel laid out for one of those accepts this unit without re-drilling the gland plate. ## Auxiliary contacts and shunt trip — what is wired in That is four discrete signal outputs for PLC status monitoring — no need to add a separate auxiliary contact block. The shunt trip (STL) release is also built in, so a remote trip signal from an E-stop or safety relay lands directly on the breaker without an external contactor. The integrated auxiliary trip (3VA9688-0BL32) and the supplied basic switch (3VA2163-7HN32-0AA0) are referenced on the nameplate. If you need to order a replacement auxiliary block, use those order codes — not the base breaker MPN. The 3VA1110-5EE32-0JA0 is a smaller-frame MCCB (100 A frame, thermal-magnetic trip) from the same SENTRON family. The 3VA2163-7HN32-0JL0 uses a 250 A frame with an electronic trip unit, so it offers adjustable protection curves and higher interrupting capacity. Physically, the 3VA1110 is narrower (70 mm vs 105 mm) and shorter, so it does not drop into the same DIN-rail footprint without a new gland plate. If your BOM calls for the 3VA1110 and you are considering this as a substitute, verify the panel cutout and the trip curve requirements first. ## Environmental range and approvals","metaTitle":"Siemens 3VA2163-7HN32-0JL0 SENTRON MCCB, 63 A, 3-Pole, ETU35","metaDescription":"Siemens 3VA2163-7HN32-0JL0 SENTRON molded case circuit breaker, 63 A, 3-pole, ETU350 release, 330 kA at 240 V. Current lifecycle stage, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"5.25 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.6375 A","at 60 °C":"58.275 A","at 65 °C":"55.9125 A","at 70 °C":"53.55 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"4 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-7HN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"756 A","Adjustable response value current / li min.":"756 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"630 A","Adjustable response value current / Isd min.":"95 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=331751&mlfb=3VA2163-7HN32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7HN32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2163-7HN32-0JL0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock count or price is published here."},{"question":"What is 3VA2163-7HN32-0JL0's interrupting capacity at 240 V?","answer":"The interrupting capacity is 330 kA at 240 V, 242 kA at 415 V, and 187 kA at 500 V. At 690 V it drops to 5.25 kA — verify system voltage before specifying."},{"question":"What auxiliary contacts are included on this breaker?","answer":"It ships with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type) — four signal outputs total. A shunt trip (STL) release is also factory-installed."},{"question":"What compliance documentation does this brand provide for 3VA2163-7HN32-0JL0?","answer":"As a Siemens SENTRON product, this MCCB carries CE marking for the European market and is designed to meet IEC 60947-2. UL and CSA listings are typical for the 3VA2 family, though the specific approvals for this order code should be confirmed from the nameplate or Siemens declaration of conformity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7HN32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7HN32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}