{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7JP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7JP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7JP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7JP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-7JP36-0AA0, molded case circuit breaker, 3-pole, 63 A, ETU550 electronic trip unit, line protection design, communication capable, IP40 front.","salesMarkdown":"## What this MCCB delivers The Siemens SENTRON 3VA2163-7JP36-0AA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C through 70 °C — no derating needed across that entire ambient span, which simplifies panel layout in warm enclosures (–,). The interrupting ratings are substantial: 330 kA at 240 V, 242 kA at 415/440 V, 187 kA at 500 V, and 3.7 kA at 690 V (–), giving it strong fault-clearing capability across common low-voltage distribution voltages. No undervoltage release is fitted, and there is no ground-fault monitoring version; those functions would need an external module or a different variant.","metaTitle":"Siemens 3VA2163-7JP36-0AA0 SENTRON MCCB, 63 A, 3-Pole, ETU55","metaDescription":"Siemens SENTRON 3VA2163-7JP36-0AA0 molded case circuit breaker, 63 A continuous, 3-pole, ETU550 trip unit, 330 kA at 240 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"756 A","Minimum":"95 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 40% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=464994&mlfb=3VA2163-7JP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7JP36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2163-7JP36-0AA0 and get a price?","answer":"We source this breaker to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ through the page and we will respond with a firm quote."},{"question":"What are the key ratings for this MCCB?","answer":"Continuous current is 63 A with no derating from 40 °C to 70 °C (–). Interrupting capacity reaches 330 kA at 240 V, 242 kA at 415/440 V, 187 kA at 500 V, and 3.7 kA at 690 V (–). The trip unit is an ETU550 electronic type, and the breaker supports communication."},{"question":"Will 3VA2163-7JP36-0AA0 drop into a panel specified around 3VA1110-5EF32-0LA0?","answer":"No — the 3VA2163-7JP36-0AA0 is a 3-pole 63 A frame with an ETU550 trip unit and communication, while the 3VA1110-5EF32-0LA0 is a different frame size and rating. Panel cutouts, bus connections, and accessory compatibility differ. Verify the mounting footprint and busbar spacing before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7JP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7JP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}