{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7MN36-0BH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7MN36-0BH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7MN36-0BH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MN36-0BH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-7MN36-0BH0, molded case circuit breaker, motor protection version, 3-pole, 63 A rated continuous current, breaking capacity 330 kA at 240 V, 242 kA at 415 V, ETU350M release, undervoltage release, phase failure detection, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"Its 63 A rated continuous current holds at ambient temperatures up to 50 °C without derating; above that the curve steps down to 60.48 A at 55 °C and 56.7 A at 70 °C, per the datasheet. The 3-pole design fits standard MCCB mounting footprints in distribution panels. It mounts into the standard MCCB cutout or on a mounting plate within an enclosure. The 105 mm width occupies one standard MCCB pole space per pole. Maximum power loss is 75 W, so ventilation or derating within sealed enclosures should be checked against the thermal curve above 50 °C.","metaTitle":"Siemens 3VA2163-7MN36-0BH0 SENTRON MCCB, 63 A, 330 kA at 240","metaDescription":"Siemens SENTRON 3VA2163-7MN36-0BH0 molded case circuit breaker, 63 A rated, 330 kA breaking capacity at 240 V. Motor protection version with ETU350M release, UVR, phase failure det","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-7MN36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"22 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"945 A","Adjustable response value current / li min.":"945 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"945 A","Adjustable response value current / Isd min.":"189 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569718&mlfb=3VA2163-7MN36-0BH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MN36-0BH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2163-7MN36-0BH0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Does 3VA2163-7MN36-0BH0 include phase failure detection?","answer":"Yes, phase failure detection is integrated into the ETU350M trip unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7MN36-0BH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7MN36-0BH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}