{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7MN36-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7MN36-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7MN36-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MN36-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-7MN36-0JA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, interrupting capacity 330 kA at 240 V, shunt trip release, ETU350M electronic trip unit.","salesMarkdown":"At 415 V and 440 V it still holds 242 kA, and at 690 V it's 52.5 kA, so it handles high-fault scenarios in industrial distribution panels where upstream transformers or large motors can dump serious energy into a fault. The electronic trip unit is an ETU350M, which gives adjustable thermal-magnetic curves plus phase-failure detection — that last bit matters for motor protection circuits where a lost phase can burn out a winding before a standard thermal overload reacts. At 55 °C it derates to 60.48 A, at 60 °C to 59.22 A, at 65 °C to 57.96 A, and at 70 °C to 56.7 A. Maximum power loss is 75 W, which is typical for a 63 A MCCB with an electronic trip unit. That heat has to leave the enclosure; plan ventilation or a larger cabinet if you're grouping several of these side by side. ## Built-in shunt trip and auxiliary options That's useful for emergency-stop circuits or remote shutdown from a PLC. The integrated auxiliary trip is a separate order code (3VA9688-0BL32), so if you need an alarm contact or status feedback, that's an add-on. If those are required, you'd step up to a different suffix in the 3VA2 family. Verify the gland plate clearance for the 86 mm depth, especially in shallow wall-mount boxes.","metaTitle":"Siemens 3VA2163-7MN36-0JA0 SENTRON MCCB, 63 A, 3-Pole, 330 k","metaDescription":"Siemens SENTRON 3VA2163-7MN36-0JA0 molded case circuit breaker, 63 A rated continuous current, 3-pole, 330 kA interrupting at 240 V. Current production. Quoted to order against RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"No","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-7MN36-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"22 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"945 A","Adjustable response value current / li min.":"945 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"945 A","Adjustable response value current / Isd min.":"189 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569732&mlfb=3VA2163-7MN36-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MN36-0JA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2163-7MN36-0JA0 at 240 V?","answer":"330 kA at 240 V, which is the highest short-circuit rating in its class — suitable for high-fault industrial distribution."},{"question":"Does 3VA2163-7MN36-0JA0 include a shunt trip?","answer":"Yes, it comes with a shunt trip release (STL) for remote tripping."},{"question":"Where can I buy 3VA2163-7MN36-0JA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7MN36-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7MN36-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}