{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7MN36-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7MN36-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7MN36-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MN36-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-7MN36-0JL0, molded case circuit breaker, motor protection version, 3-pole, 63 A rated continuous current, ETU350M electronic trip unit, 330 kA breaking capacity at 240 V.","salesMarkdown":"Rated continuous current Iu is 63 A, and it holds that rating from 40 °C up to 50 °C; above that it derates to 60.48 A at 55 °C and 56.7 A at 70 °C, so a warm panel or high-ambient motor center needs a check against the thermal curve before committing the BOM line. Breaking capacity is voltage-dependent: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V — that covers most industrial distribution voltages across North America and Europe, and the 690 V figure matters for wind or mining applications where the line-to-line voltage is higher. Three-pole, 105 mm wide, 181 mm tall, 86 mm deep — it occupies a standard SENTRON 3VA mounting footprint, so it swaps into an existing 3VA panel cutout without re-drilling the gland plate. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C — fine for unheated warehouses in northern climates as long as the breaker is not energized below -25 °C.","metaTitle":"Siemens 3VA2163-7MN36-0JL0 SENTRON MCCB, 63 A, 3-Pole, Motor","metaDescription":"Siemens SENTRON 3VA2163-7MN36-0JL0 molded case circuit breaker, 63 A rated, 3-pole, motor protection version with ETU350M release. Breaking capacity 330 kA at 240 V. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-7MN36-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"22 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"945 A","Adjustable response value current / li min.":"945 A","Adjustable response value current / lr min.":"25 A","Adjustable response value current / Isd max.":"945 A","Adjustable response value current / Isd min.":"189 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569735&mlfb=3VA2163-7MN36-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MN36-0JL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2163-7MN36-0JL0 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2163-7MN36-0JL0 at different voltages?","answer":"Breaking capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V."},{"question":"Does 3VA2163-7MN36-0JL0 include phase failure detection?","answer":"Yes, the ETU350M electronic trip unit includes phase failure detection, making it suitable for motor protection applications where loss of a phase must trip the breaker."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7MN36-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7MN36-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}