{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7MN36-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7MN36-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7MN36-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MN36-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3-pole, 63 A, motor protection design, 330 kA breaking capacity at 240 V, shunt trip release, auxiliary switches.","salesMarkdown":"## Motor Protection MCCB — 63 A, 330 kA IC at 240 V Breaking capacity reaches 330 kA at 240 V, 242 kA at 415/440 V, and 187 kA at 500 V — high enough for most industrial fault-current scenarios downstream of a large transformer. ## Integrated Auxiliaries and Releases The basic switch itself is order code 3VA2163-7MN36-0AA0; the -0KH0 suffix adds the auxiliaries and shunt trip as a configured variant, saving panel wiring time. No undervoltage release fitted, no ground-fault monitoring, and no communication function — this is a straightforward motor-protection breaker, not a power-monitoring device. ## Panel Fit and Environment Maximum power dissipation 4 W, manageable in a sealed enclosure without forced cooling. Trip indicator and voltage trigger are present — the indicator shows the breaker has tripped on fault, not just been switched off manually.","metaTitle":"Siemens 3VA2163-7MN36-0KH0 SENTRON MCCB, 63 A, 3-Pole, Motor","metaDescription":"Siemens 3VA2163-7MN36-0KH0 SENTRON molded case circuit breaker, 63 A rated current, 3-pole motor protection, 330 kA breaking capacity at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2163-7MN36-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"18 500 W","operating power / at AC-3 / at 400 V":"30 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569738&mlfb=3VA2163-7MN36-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MN36-0KH0/alternatives.json"},"ai":{"faq":[{"question":"What auxiliaries come fitted on this MCCB?","answer":"A shunt trip release (STL) plus 2 auxiliary switches and 1 trip alarm switch (HQ) are factory-installed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7MN36-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7MN36-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}