{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7MS32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7MS32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7MS32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MS32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-7MS32-0JC0, molded case circuit breaker, 3-pole, 63 A, 330 kA at 240 V, starter protection with ETU310M.","salesMarkdown":"This MCCB delivers 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V. Rated 63 A from 40 °C through 50 °C ambient; above that it steps down: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. If the panel sits near ovens or in a non-vented enclosure, use the 55 °C or 60 °C row for your continuous load calculation. Depth 86 mm, width 105 mm, height 181 mm — standard 3-pole MCCB footprint for SENTRON 3VA2 frames. The 105 mm width matches the typical 4-module DIN-rail pitch, so it slots into a multi-breaker lineup without odd spacing. Depth of 86 mm leaves clearance behind a 200 mm deep enclosure door.","metaTitle":"Siemens 3VA2163-7MS32-0JC0 MCCB, 63 A, 330 kA at 240 V","metaDescription":"Siemens SENTRON 3VA2163-7MS32-0JC0 molded case circuit breaker, 63 A, 330 kA interrupting at 240 V. Starter protection with ETU310M. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"No","Number of poles":"3","Product version":"Starter protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2163-7MS32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU310M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"22 W","Reference code / acc. to DIN EN 81346-2":"Q","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"0 A","Adjustable response value current / li max.":"945 A","Adjustable response value current / li min.":"189 A","Adjustable response value current / lr min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"I","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569768&mlfb=3VA2163-7MS32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MS32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Is 3VA2163-7MS32-0JC0 available via RFQ confirmation and what is the lead time?","answer":"The part is sourced to order against an RFQ. Stock status and lead time are confirmed at quote time — submit an RFQ for current availability."},{"question":"What is 3VA2163-7MS32-0JC0's interrupting capacity at 415 V?","answer":"242 kA at 415 V, which covers most European industrial fault levels."},{"question":"What compliance documentation does this brand provide for 3VA2163-7MS32-0JC0?","answer":"Siemens SENTRON MCCBs typically carry UL, CSA, CE, and IEC certifications; specific documentation (RoHS, REACH) is available on request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7MS32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7MS32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}