{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2163-7MS36-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2163-7MS36-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2163-7MS36-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MS36-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2163-7MS36-0HA0, Molded case circuit breaker, 3-pole, 63 A, 330 kA at 240 V, 242 kA at 415 V, 187 kA at 500 V, 3.7 kA at 690 V, shunt trip release, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"## SENTRON 3VA2163-7MS36-0HA0 — MCCB for motor and feeder protection The Siemens SENTRON 3VA2163-7MS36-0HA0 is a 3-pole molded case circuit breaker (MCCB) rated 63 A continuous across the full 40 °C to 70 °C ambient range — no derating needed in a hot panel. It carries a 330 kA interrupting capacity at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V. ## Panel integration and dimensions The breaker occupies 105 mm width, 181 mm height, and 86 mm depth — fits standard MCCB panel cutouts. No auxiliary switch or undervoltage release is included, so plan separate wiring for those functions if needed.","metaTitle":"Siemens SENTRON 3VA2163-7MS36-0HA0 MCCB, 63 A, 3-pole, 330 k","metaDescription":"Siemens SENTRON 3VA2163-7MS36-0HA0 molded case circuit breaker, 63 A, 3-pole, 330 kA at 240 V. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"945 A","Minimum":"189 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"63 A","at 60 °C":"63 A","at 65 °C":"63 A","at 70 °C":"63 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Starter protection","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2163-7MS36-0AA0","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"63 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU310M","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b27f8f8fa25a6619d6d76a928fe2e8a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569796&mlfb=3VA2163-7MS36-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2163-7MS36-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of this MCCB?","answer":"330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V — confirm the available fault current at your system voltage."},{"question":"Where can I buy 3VA2163-7MS36-0HA0?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for current availability and pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2163-7MS36-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2163-7MS36-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}