{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-5HL32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-5HL32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-5HL32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HL32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2216-5HL32-0JH0, 3-pole molded case circuit breaker, 160 A continuous, adjustable 240–1920 A, 187 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2216-5HL32-0JH0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current, with an adjustable overload trip range from 240 A to 1920 A. Breaking capacity is substantial: 187 kA at 240 V, 121 kA at 415 V and 440 V, dropping to 75.6 kA at 500 V, and 4.5 kA at 690 V. The trip indicator and voltage trigger are present; undervoltage release and ground-fault monitoring are not fitted on this variant. Depth of 86 mm means it clears most standard enclosure backplates, but check your gland plate clearance if the breaker sits near the rear wall. Maximum power loss is 19.7 W, so factor that into your enclosure thermal budget — especially if multiple breakers are ganged in a sealed cabinet.","metaTitle":"Siemens 3VA2216-5HL32-0JH0 SENTRON MCCB, 160 A, 3-Pole, 1920","metaDescription":"Siemens SENTRON 3VA2216-5HL32-0JH0 molded case circuit breaker. 3-pole, 160 A continuous, adjustable 240-1920 A, 187 kA at 240 V. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 920 A","Minimum":"240 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"4.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2216-5HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=315496&mlfb=3VA2216-5HL32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HL32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"What is the continuous current rating of this breaker?","answer":"160 A continuous, and it holds that rating across the full operating temperature range from -25 °C to 70 °C without derating."},{"question":"Does this breaker include a shunt trip?","answer":"Yes, it has a shunt trip (STL) release for remote tripping via a control signal. It also includes two auxiliary switches and one trip alarm switch for status feedback."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-5HL32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-5HL32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}