{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-5HL42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-5HL42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-5HL42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HL42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2216-5HL42-0AA0, molded case circuit breaker, 4-pole, 160 A continuous, ETU320 electronic trip unit, line protection design.","salesMarkdown":"## What this 160 A MCCB delivers The Siemens SENTRON 3VA2216-5HL42-0AA0 is a 4-pole molded case circuit breaker rated for 160 A continuous current, carrying that rating flat from 40 °C through 70 °C ambient — no derating curve to chase in a warm enclosure. Insulation voltage is rated 800 V, and the interrupting capacity hits 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 4.5 kA at 690 V — a steep SCCR curve that matters when you're coordinating with upstream gear. Maximum power loss is 19.7 W. Lifecycle stage is listed as current — no phase-out notice, no last-time-buy window.","metaTitle":"Siemens SENTRON 3VA2216-5HL42-0AA0 MCCB, 160 A, 4-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2216-5HL42-0AA0 molded case circuit breaker. 160 A continuous, 4-pole, ETU320 trip unit, 187 kA at 240 V. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"1 920 A","Minimum":"240 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"4.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 50%; 100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=43396&mlfb=3VA2216-5HL42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HL42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2216-5HL42-0AA0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request with your quantity and target delivery window; availability and current pricing are confirmed at quote time."},{"question":"What is 3VA2216-5HL42-0AA0's interrupting capacity at 415 V?","answer":"The interrupting capacity is 121 kA at 415 V, and the same at 440 V. At 240 V it reaches 187 kA; at 500 V it drops to 75.6 kA; at 690 V it is 4.5 kA."},{"question":"What trip unit does this MCCB use?","answer":"It uses the ETU320 electronic trip unit, with an adjustable overload pickup range from 240 A to 1,920 A."},{"question":"Will 3VA2216-5HL42-0AA0 drop into a panel specified around 5SQ2670-2YA06 without rewiring?","answer":"The 5SQ2670-2YA06 series shares the same frame size and trip range, making it the closest functional peer. However, terminal arrangement and accessory compatibility should be verified before direct substitution — the mounting footprint is the same, but accessory slots and wiring lug positions may differ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-5HL42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-5HL42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}