{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-5HN32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-5HN32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-5HN32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HN32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 250 MCCB, breaking capacity class M, Icu=55kA @ 415V, 3-pole, ETU350 LSI trip unit, In=160A, Ir=63A...160A, Isd=1.5...10 x Ir, Ii=12 x In, with 2 auxiliary switches and 1 trip alarm switch.","salesMarkdown":"## What this 3VA2 breaker brings to the panel This SCCR headroom is what lets you coordinate it downstream of a higher-rated main breaker and still meet the short-circuit rating required by IEC 60947-2. The continuous current rating (In) is 160 A, with the overload protection (Ir) adjustable from 63 A to 160 A. Short-circuit protection (Isd) is set between 1.5 and 10 times Ir, and the instantaneous pickup (Ii) is fixed at 12 times In. That LSI curve — long-time, short-time, instantaneous — gives the selectivity needed to coordinate with downstream branch breakers and avoid nuisance tripping on motor-start inrush or transformer energization. Two auxiliary switches (changeover H) and one trip alarm switch (changeover) are factory-fitted, so you get remote status indication and a separate alarm contact for fault annunciation without adding accessory modules. ## Deployment context: where this breaker fits This MCCB is sized for a 160 A feeder or large motor branch in a 415 V industrial panel. The 3-pole format suits three-phase loads: pumps, compressors, conveyors, or a distribution sub-panel. The ETU350's LSI curve lets you set short-time delay for selectivity with downstream breakers, which is critical in a multi-level distribution scheme.","metaTitle":"Siemens 3VA2216-5HN32-0AH0 Circuit Breaker, 55kA @ 415V, 160","metaDescription":"Siemens 3VA2216-5HN32-0AH0 IEC frame 250 MCCB, 55kA breaking capacity at 415V, 160A In, ETU350 LSI protection. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1502250&mlfb=3VA2216-5HN32-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HN32-0AH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2216-5HN32-0AH0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of the 3VA2216-5HN32-0AH0?","answer":"It is a 3-pole MCCB on the 250 A frame with a 55 kA interrupting capacity at 415 V, 160 A continuous rating (In), and an ETU350 LSI electronic trip unit with adjustable Ir (63 A to 160 A) and Isd (1.5 to 10 x Ir), plus a fixed Ii of 12 x In."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-5HN32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-5HN32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}