{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-5HN32-0BD0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-5HN32-0BD0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-5HN32-0BD0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HN32-0BD0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 250, breaking capacity class M, 55kA @ 415V, 3-pole, ETU350 LSI, In=160A, Ir=63-160A, UVR 24V DC, 3 aux switches.","salesMarkdown":"## What this 3VA2 breaker carries The continuous current rating (In) is 160 A, with the long-time pickup (Ir) adjustable from 63 A to 160 A, so it covers a 63–160 A feeder or main breaker slot in a panel. Short-time pickup (Isd) is set from 1.5 to 10 times Ir, and instantaneous pickup (Ii) is fixed at 12 times In — a deliberate coordination curve for distribution panels where you need selective tripping downstream. ## Integration notes The UVR coil draws from a 24 V DC control supply — verify polarity and that the supply can hold the coil energized continuously; dropout voltage is typically below 18 V DC. The three auxiliary switches (HQ) provide N/O + N/C contact sets for PLC or SCADA feedback, wired to the breaker's accessory slot.","metaTitle":"Siemens 3VA2216-5HN32-0BD0 Circuit Breaker, 55kA @ 415V, 160","metaDescription":"Siemens 3VA2216-5HN32-0BD0 IEC frame 250 circuit breaker, 55kA breaking capacity @ 415V, ETU350 LSI trip, 160A. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=576187&mlfb=3VA2216-5HN32-0BD0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HN32-0BD0/alternatives.json"},"ai":{"faq":[{"question":"What are the key trip settings on this breaker?","answer":"The ETU350 LSI trip unit provides long-time pickup (Ir) adjustable 63–160 A, short-time pickup (Isd) 1.5–10 x Ir, and instantaneous pickup (Ii) fixed at 12 x In (1920 A)."},{"question":"Where can I buy 3VA2216-5HN32-0BD0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-5HN32-0BD0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-5HN32-0BD0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}