{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-5HN32-0KG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-5HN32-0KG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-5HN32-0KG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HN32-0KG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 250, breaking capacity class M, 3-pole, line protection ETU350 LSI, In=160A, Icu=55kA @ 415V, with shunt trip STL 220-250V DC / 208-277V AC, 1 auxiliary switch HP, 1 trip alarm switch HP, nut keeper kit.","salesMarkdown":"The Siemens 3VA2216-5HN32-0KG0 is a 3-pole IEC molded case circuit breaker from the 3VA2 series, frame size 250, with a breaking capacity class M rated at 55 kA at 415 V AC. It carries an ETU350 LSI trip unit, adjustable overload protection Ir from 63 A to 160 A, and short-circuit protection Isd from 1.5 to 10 times Ir, with instantaneous pickup Ii at 12 times In. This variant includes a shunt trip (STL) rated for 220-250 V DC or 208-277 V AC, one auxiliary switch HP, one trip alarm switch HP, and a nut keeper kit. The ETU350 LSI trip unit provides electronic adjustable long-time (L), short-time (S), and instantaneous (I) protection, letting you fine-tune the curve to the load. The 160 A frame with Ir adjustable down to 63 A gives flexibility to match downstream cable or motor ratings without swapping the breaker body. ## Integration Notes Mounts in a standard panel on DIN rail or via the 3VA mounting plate. The shunt trip coil draws from a separate control circuit — verify polarity on the DC version (220-250 V DC) and that the AC supply matches the 208-277 V AC range. The nut keeper kit retains the line/load lug fasteners during high-vibration environments like near motor starters or transformer feeds.","metaTitle":"Siemens 3VA2216-5HN32-0KG0 Circuit Breaker, 160A, 55kA @ 415","metaDescription":"Siemens 3VA2216-5HN32-0KG0 IEC frame 250, 3-pole, ETU350 LSI, 160A, 55kA breaking capacity at 415V. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=558682&mlfb=3VA2216-5HN32-0KG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5HN32-0KG0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"The ultimate short-circuit breaking capacity (Icu) is 55 kA at 415 V AC, classification class M per IEC."},{"question":"Where can I buy 3VA2216-5HN32-0KG0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What does the ETU350 LSI trip unit cover?","answer":"The ETU350 provides electronic long-time (L), short-time (S), and instantaneous (I) protection. Overload Ir is adjustable from 63 A to 160 A, short-time pickup Isd from 1.5 to 10 x Ir, and instantaneous Ii is fixed at 12 x In."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-5HN32-0KG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-5HN32-0KG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}