{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-5MP32-0DK0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-5MP32-0DK0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-5MP32-0DK0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5MP32-0DK0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 250 MCCB, breaking capacity class M Icu=55kA @ 415 V, 3-pole, motor protection ETU550M LSI, In=160A, overload protection Ir=64A…160A, short-circuit protection Isd=1.2…15x In, Ii=3…15x In.","salesMarkdown":"The In rating is 160 A, with overload protection (Ir) adjustable from 64 A to 160 A, and short-circuit protection (Isd) from 1.2 to 15 times In, plus instantaneous (Ii) from 3 to 15 times In. That adjustability lets you fine-tune the trip to the motor's locked-rotor and starting inrush without nuisance tripping. ## Built-in accessories and deployment context The busbar connection and the accessory set are pre-configured for the 3VA1 platform, so it drops into a panel with the same mounting footprint. For a motor control center or a dedicated pump/conveyor feeder, the undervoltage release provides automatic dropout on supply loss — no separate control relay needed.","metaTitle":"Siemens 3VA2216-5MP32-0DK0 Circuit Breaker, 55kA @ 415V, 160","metaDescription":"Siemens 3VA2216-5MP32-0DK0 IEC frame 250 MCCB, 55kA breaking capacity at 415V, 3-pole, motor protection ETU550M LSI, In=160A. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1541253&mlfb=3VA2216-5MP32-0DK0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-5MP32-0DK0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB?","answer":"The breaking capacity is 55 kA at 415 V (class M), which is the Icu rating for this IEC frame 250 breaker."},{"question":"What trip unit does this breaker use?","answer":"It uses an ETU550M electronic trip unit with LSI protection — long-time, short-time, and instantaneous — adjustable for motor protection."},{"question":"Where can I buy 3VA2216-5MP32-0DK0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-5MP32-0DK0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-5MP32-0DK0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}