{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-6HK32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-6HK32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-6HK32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-6HK32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA2216-6HK32-0AA0, molded case circuit breaker, 3-pole, 160 A, ETU340 electronic trip unit, line protection, 242 kA at 240 V, 187 kA at 415 V, IP40 front.","salesMarkdown":"The SENTRON 3VA2216-6HK32-0AA0 is a 3-pole molded case circuit breaker rated 160 A continuous (no derating from 40 °C to 70 °C) with an ETU340 electronic trip unit configured for line protection. The IP40 front face suits panel-mount applications where the enclosure provides the environmental seal. It's the same platform used across the 3VA2 family, so settings and test procedures are consistent if you're standardizing on SENTRON breakers.","metaTitle":"SENTRON 3VA2216-6HK32-0AA0 MCCB, 160 A, 3-Pole, ETU340, 242","metaDescription":"SENTRON 3VA2216-6HK32-0AA0 molded case circuit breaker, 160 A, 3-pole, ETU340 electronic trip unit, 242 kA at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"160 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU340","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"2 400 A","Adjustable response value current / li min.":"2 400 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"ELISA LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"250 A","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=173107&mlfb=3VA2216-6HK32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-6HK32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the interrupting ratings for 3VA2216-6HK32-0AA0?","answer":"242 kA at 240 V, 187 kA at 415 V and at 440 V, 121 kA at 500 V, and 4.5 kA at 690 V. These are symmetric RMS values; the 690 V figure drops sharply, so confirm system voltage before specifying."},{"question":"Will 3VA2216-6HK32-0AA0 drop into a panel designed for 3VA1112-5EE32-0AA0?","answer":"No — the 3VA2 frame is physically larger than the 3VA1 frame. The 3VA2216-6HK32-0AA0 is 105 mm wide versus the 3VA1's narrower footprint, so the mounting holes and bus-bar spacing differ. A panel laid out for a 3VA1 won't accept this breaker without rework."},{"question":"How do I get current pricing and availability for 3VA2216-6HK32-0AA0?","answer":"Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time; this part is sourced through independent distribution channels."},{"question":"What compliance documentation does SENTRON provide for 3VA2216-6HK32-0AA0?","answer":"Standard documentation includes the manufacturer's declaration of conformity to IEC 60947-2, RoHS and REACH compliance statements, and a detailed technical datasheet. These are available on request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-6HK32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-6HK32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}