{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-6HM32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-6HM32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-6HM32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-6HM32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2216-6HM32-0AA0, molded case circuit breaker, 160 A, 3-pole, ETU330 electronic trip unit, 242 kA at 240 V.","salesMarkdown":"The Siemens 3VA2216-6HM32-0AA0 is a SENTRON molded case circuit breaker rated for 160 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed until you push past 70 °C. That 160 A holds steady at every 5 °C step from 40 up to 70 °C, so it handles warm enclosures without a second look at the thermal curve. Breaking capacity hits 242 kA at 240 V AC, dropping to 187 kA at 415 V and 440 V, then 121 kA at 500 V, and 4.5 kA at 690 V. The ETU330 electronic trip unit gives adjustable I²t protection (the design of I-trip is adjustable), so you can shape the long-time and short-time pickup to match your feeder or motor branch circuit. No voltage trigger, no undervoltage release, no communication module — this is a straight line-protection breaker with ground-fault monitoring via summation current on the L-conductors.","metaTitle":"Siemens 3VA2216-6HM32-0AA0 SENTRON MCCB, 160 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2216-6HM32-0AA0 molded case circuit breaker, 160 A, 3-pole, ETU330 electronic trip unit. 242 kA at 240 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"160 A","design of I-trip / adjustable":"Yes","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU330","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg max.":"160 A","Adjustable response value current / lg min.":"32 A","Adjustable response value current / li max.":"1 920 A","Adjustable response value current / li min.":"240 A","let-through energy characteristic / at 240 V":"DE_3VA2_2_160A_ETU_line u starter u motor_3u4p_240V","let-through energy characteristic / at 415 V":"DE_3VA2_2_160A_ETU_line u starter u motor_3u4p_415V","let-through energy characteristic / at 440 V":"DE_3VA2_2_160A_ETU_line u starter u motor_3u4p_440V","let-through energy characteristic / at 500 V":"DE_3VA2_2_160A_ETU_line u starter u motor_3u4p_500V","let-through energy characteristic / at 690 V":"DE_3VA2_2_160A_ETU_line u starter u motor_3u4p_690V","product feature / for G-tripping / adjustable":"Yes","product feature / for L-tripping / adjustable":"Yes","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","set values setting current (Ii) / for I-tripping":"1.5;2;2.5;3;4;5;6;8;10;12","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Tripping Characteristic / Of The Lower Tolerance Band":"AK_3VA2_2_160A_ETU320u330_MuHuCuL_uT","Tripping Characteristic / Of The Upper Tolerance Band":"AK_3VA2_2_160A_ETU320u330_MuHuCuL_oT","reference value setting current (Ii) / for I-tripping":"x In","reference value setting current (InN) / for N-tripping":"x In","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","type of value list setting current (Ii) / for I-tripping":"St","type of value list setting current (InN) / for N-tripping":"St","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=183312&mlfb=3VA2216-6HM32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-6HM32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at 240 V?","answer":"242 kA at 240 V AC. That rating drops to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V."},{"question":"Where can I buy 3VA2216-6HM32-0AA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-6HM32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-6HM32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}