{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-6JP32-0KF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-6JP32-0KF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-6JP32-0KF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-6JP32-0KF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2216-6JP32-0KF0, 3-pole molded case circuit breaker, line protection, 160 A continuous, 242 kA breaking at 240 V, 86 x 105 x 181 mm.","salesMarkdown":"The Siemens SENTRON 3VA2216-6JP32-0KF0 is a 3-pole molded case circuit breaker rated 160 A continuous from 40 °C to 70 °C — no derating across that band, which simplifies panel design in warm enclosures. Breaking capacity hits 242 kA at 240 V and 187 kA at 415 V, so it handles high-fault utility feeds without cascading upstream breakers — a real advantage for main or tie applications where SCCR headroom is tight. Rated minimum 240 A and maximum 1 920 A define the magnetic trip range; the unit ships with a shunt trip release (STL) and one auxiliary switch plus one trip alarm switch HQ, giving the panel builder remote status and emergency trip without adding external relays. Communication function is built in, supporting integration with higher-level monitoring — no separate comm module needed. Measures 86 mm deep, 105 mm wide, 181 mm tall — a compact footprint for a 160 A MCCB, fitting standard distribution panel cutouts without special adapters. Operating range from -25 °C to 70 °C; storage from -40 °C to 80 °C. Maximum power loss 19.7 W — thermal management straightforward in a ventilated enclosure. Breaking capacities: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, 4.5 kA at 690 V.","metaTitle":"Siemens 3VA2216-6JP32-0KF0 MCCB, 160 A, 242 kA at 240 V","metaDescription":"Siemens SENTRON 3VA2216-6JP32-0KF0 molded case circuit breaker, 160 A rated, 3-pole, 242 kA at 240 V. Active production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 920 A","Minimum":"240 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"#BEZUG!","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=808492&mlfb=3VA2216-6JP32-0KF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-6JP32-0KF0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA2216-6JP32-0KF0 include a shunt trip?","answer":"Yes, it ships with a shunt trip release (STL) plus one auxiliary switch and one trip alarm switch HQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-6JP32-0KF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-6JP32-0KF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}