{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-7JP32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-7JP32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-7JP32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7JP32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 250, circuit breaker, 3-pole, breaking capacity class C Icu=110kA @ 415V, ETU550 LSI trip unit, In=160A, overload Ir=63..160A, with 2 auxiliary switches changeover + 1 trip alarm changeover.","salesMarkdown":"The Siemens 3VA2216-7JP32-0AH0 is a 3-pole IEC frame 250 molded case circuit breaker rated for 160 A continuous current, with a class C breaking capacity of 110 kA at 415 V AC. It carries the ETU550 electronic trip unit configured for LSI protection (long-time, short-time, instantaneous). Overload protection (Ir) is adjustable from 63 A to 160 A; short-time pickup (Isd) spans 0.6–10× In; instantaneous (Ii) covers 1.5–12× In. The breaker ships with a 2-pole auxiliary switch changeover and a separate trip alarm changeover contact. Mounts in a standard IEC 60947-2 panelboard or distribution enclosure on the DIN-rail or screw-fixed chassis. The ETU550 is line-powered — no external control voltage needed for the trip unit. The auxiliary and alarm contacts are pre-wired to the terminal block; confirm the changeover wiring matches your PLC or status-indication circuit before closing the breaker. Neutral conductor protection is available as an option with an external current transformer, up to 160 % of the phase rating.","metaTitle":"Siemens 3VA2216-7JP32-0AH0 160A MCCB, 110kA @ 415V","metaDescription":"Siemens 3VA2 IEC frame 250 MCCB, 160 A, 110 kA breaking capacity @ 415 V AC, ETU550 LSI trip unit. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1536919&mlfb=3VA2216-7JP32-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7JP32-0AH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2216-7JP32-0AH0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this MCCB?","answer":"Rated Icu of 110 kA at 415 V AC, class C per IEC 60947-2, which means it safely interrupts faults up to that level without upstream cascading."},{"question":"What trip unit is fitted on 3VA2216-7JP32-0AH0?","answer":"An ETU550 electronic trip unit with LSI protection: long-time (Ir 63–160 A), short-time (Isd 0.6–10× In), and instantaneous (Ii 1.5–12× In)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-7JP32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-7JP32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}