{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-7MN32-0AD0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-7MN32-0AD0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0AD0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0AD0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2216-7MN32-0AD0, molded case circuit breaker, 3-pole, 160 A, ETU350M electronic trip unit, 330 kA breaking capacity at 240 V.","salesMarkdown":"It is a motor-protection version with phase-failure detection built in, so it catches the unbalanced load condition that cooks windings before the thermal curve would trip. Three auxiliary switches (HQ type) are integrated for remote status feedback — no separate add-on block needed for basic signaling. Breaking capacity is 330 kA at 240 V and 242 kA at 415/440 V, tapering to 187 kA at 500 V and 52.5 kA at 690 V. Above that it derates stepwise: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. Maximum power loss is 75 W — that heat has to leave the enclosure, so factor it into the thermal budget. If your application needs undervoltage or ground-fault protection, that requires a different variant or an add-on module.","metaTitle":"Siemens 3VA2216-7MN32-0AD0 SENTRON MCCB, 160 A, 3-Pole, ETU3","metaDescription":"Siemens 3VA2216-7MN32-0AD0 SENTRON molded case circuit breaker, 160 A rated continuous current, 3-pole, ETU350M trip unit, 330 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"No","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"3 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2216-7MN32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"55 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"2 400 A","Adjustable response value current / li min.":"2 400 A","Adjustable response value current / lr min.":"63 A","Adjustable response value current / Isd max.":"2 400 A","Adjustable response value current / Isd min.":"480 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570034&mlfb=3VA2216-7MN32-0AD0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0AD0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB?","answer":"330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V. The 330 kA rating at 240 V is the highest figure — suitable for high-fault installations."},{"question":"What trip unit does the 3VA2216-7MN32-0AD0 use?","answer":"It uses the ETU350M electronic trip unit (order code 3VA9608-0BB24). This is a motor-protection release with phase-failure detection."},{"question":"Where can I buy 3VA2216-7MN32-0AD0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0AD0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-7MN32-0AD0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}