{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-7MN32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-7MN32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2216-7MN32-0CC0, molded case circuit breaker, 3-pole, 160 A, motor protection design, 330 kA breaking at 240 V, with undervoltage release and 2 auxiliary switches HQ.","salesMarkdown":"Breaking capacity is 330 kA at 240 V AC, dropping to 242 kA at 415 V and 440 V, then 187 kA at 500 V, and 4.5 kA at 690 V — the high interrupt ratings at common distribution voltages (240–500 V) mean this breaker can sit at the main or sub-main of a high-fault industrial panel without needing a current-limiting upstream device. If you're cross-referencing from an older panel that used 5SQ2370-2YA05 or similar, the 3VA2216-7MN32-0CC0 is a different generation and footprint; a drop-in without rewiring is not guaranteed. The 86 mm depth, 105 mm width, and 181 mm height match the 3VA2 frame standard, so panel cutout and mounting dimensions should be verified against the existing breaker's footprint. That simplifies panel design: if your motor FLA is 150 A and the ambient inside the enclosure hits 65 °C, this breaker still holds 160 A without nuisance tripping. Three-pole design with phase failure detection means it opens on loss of any one phase — critical for motor protection because single-phasing a running motor can cause winding damage.","metaTitle":"Siemens 3VA2216-7MN32-0CC0 SENTRON MCCB, 160 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2216-7MN32-0CC0 SENTRON molded case circuit breaker, 160 A continuous, 330 kA at 240 V, 3-pole motor protection with undervoltage release. Current lifecycle stage, avail","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"4.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"22.2 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2216-7MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"45 000 W","operating power / at AC-3 / at 400 V":"75 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570045&mlfb=3VA2216-7MN32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2216-7MN32-0CC0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What are the key ratings of 3VA2216-7MN32-0CC0?","answer":"Continuous rating is 160 A from 40 °C to 70 °C ambient. Breaking capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 4.5 kA at 690 V. It is a 3-pole motor-protection MCCB with phase failure detection and an undervoltage release."},{"question":"Will 3VA2216-7MN32-0CC0 drop into a panel specified around 5SQ2370-2YA05?","answer":"Not guaranteed without verification. The 3VA2216-7MN32-0CC0 is a different generation and frame size from the 5SQ2370 series. Its dimensions are 86 mm depth, 105 mm width, and 181 mm height — compare these against the existing breaker's cutout and mounting before assuming a direct swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-7MN32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}