{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2216-7MN32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2216-7MN32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2216-7MN32-0CL0, molded case circuit breaker, 3-pole, 160 A rated continuous current Iu, motor protection version with ETU350M electronic release, 330 kA breaking capacity at 240 V.","salesMarkdown":"The ETU350M electronic overcurrent release gives you adjustable thermal and magnetic trip curves, plus phase failure detection, so it catches a lost phase before the motor cooks. At 415 V and 440 V it still holds 242 kA, and at 690 V it drops to 52.5 kA, which still covers most motor branch circuits. The breaker holds 160 A flat from 40 °C through 50 °C, then derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. Maximum power loss is 75 W, so factor that into the enclosure thermal budget.","metaTitle":"Siemens 3VA2216-7MN32-0CL0 SENTRON MCCB, 160 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2216-7MN32-0CL0 molded case circuit breaker, 160 A rated at 40 °C, 3-pole, motor protection with ETU350M release. Breaking capacity 330 kA at 240 V. Sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"153.6 A","at 60 °C":"150.4 A","at 65 °C":"147.2 A","at 70 °C":"144 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2216-7MN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"55 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"2 400 A","Adjustable response value current / li min.":"2 400 A","Adjustable response value current / lr min.":"63 A","Adjustable response value current / Isd max.":"2 400 A","Adjustable response value current / Isd min.":"480 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/925896f022f1bf1dfe799568fd778a5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570047&mlfb=3VA2216-7MN32-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2216-7MN32-0CL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2216-7MN32-0CL0 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2216-7MN32-0CL0 at 240 V?","answer":"The breaking capacity is 330 kA at 240 V."},{"question":"What is the rated continuous current Iu of this MCCB?","answer":"The rated continuous current Iu is 160 A at 40 °C."},{"question":"Does 3VA2216-7MN32-0CL0 include phase failure detection?","answer":"Yes, the ETU350M release includes phase failure detection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2216-7MN32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2216-7MN32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}